Final | 11/13/2001 | 11/13/2001 | 11/13/2001 | A | PASS |
Alan Hauser
|
|
|
Scheduled by Inspector: 350 On 11/13/2001 12:00:07 PM
|
DOC - Permit Finaled | 11/13/2001 | 11/13/2001 | 11/13/2001 | P | PASS |
Alan Hauser
|
|
|
Finaled by inspector at 11/13/2001 12:03:00 PM
|
Rough-in | 11/9/2001 | 11/9/2001 | 11/9/2001 | P | PART |
Alan Hauser
|
|
|
duct wrap at grease ducts ok, still finishing third one 11/9/2001 1:11:42 PM
|
Rough-in | 11/8/2001 | 11/8/2001 | 11/8/2001 | A | PART |
Alan Hauser
|
|
|
grease ducts ok, question on duct wrap to be used, called engineer and he is looking into new product use in r.a. plenum, specs. don't meet smoke developement rating for r.a. plenum 11/8/2001 10:19:57 AM
|
Application received | | | 10/31/2001 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/31/2001 | | DONE |
|
|
|
|