DOC - Permit Finaled | 2/11/2003 | 2/11/2003 | 2/11/2003 | A | PASS |
Alan Hauser
|
|
|
Finaled by inspector at 2/11/2003 7:38:16 PM
|
Final | 2/10/2003 | 2/10/2003 | 2/10/2003 | P | PASS |
Alan Hauser
|
|
|
added condensate pump for proper drainage, until next cooling season, won't know if pump works. at this time all pieces in place and appears it should remove condensate water. 2/11/2003 7:38:15 PM
|
Final | 1/28/2003 | 1/29/2003 | 1/29/2003 | A | FAIL |
Russ Owen
|
|
|
les--; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Condensate drains up hill approx 1 foot in 10 foot , pan in coil will not hold this amount of water before draining out. minimum 1/8 per foot slope required left a c/n with home owner. 1/29/2003 9:43:32 AM
|
Rough-in | 11/8/2002 | 11/8/2002 | 11/8/2002 | P | PASS |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
Rough-in | 11/6/2002 | 11/6/2002 | 11/6/2002 | P | FAIL |
Dixie Fellows
|
|
|
les- ###-#### REMOVE FOIL TAPE FROM AROUND B-VENT AS TALKED ABOUT BEFORE 11/6/2002 5:54:04 PM
|
Rough-in | 10/31/2002 | 11/1/2002 | 11/1/2002 | A | PART |
Dixie Fellows
|
|
|
les-per dixie will meet with ladder; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie gas only...r/i not ready 11/1/2002 9:16:20 AM
|
Rough-in | 10/31/2002 | 10/31/2002 | 10/31/2002 | P | FAIL |
Dixie Fellows
|
|
|
LES ; Phone #: ###-#### Internet Inspection Request from: Darla Downs need access to attic...ladder is to short 10/31/2002 2:21:47 PM
|
Pressure Test | 10/31/2002 | 10/31/2002 | 10/31/2002 | P | FAIL |
Dixie Fellows
|
|
|
LES ; Phone #: ###-#### Internet Inspection Request from: Darla Downs called les 10/31/2002 2:22:02 PM
|
Rough-in | 10/23/2002 | 10/24/2002 | 10/24/2002 | A | FAIL |
Dave Hannah
|
|
|
access in attic\\###-#### furnace in attic light switch elec out let cons drains passage way insulate boots and plenums 10/24/2002 11:34:05 AM
|
Application received | | | 10/23/2002 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/23/2002 | | DONE |
|
|
|
|