Third Notice MEC | 10/15/2003 | 10/15/2003 | 5/7/2004 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice MEC | 9/25/2003 | 9/25/2003 | 10/15/2003 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 7/23/2003 | 9/25/2003 | | DONE |
|
|
|
|
DOC - Permit Finaled | 7/23/2003 | 7/23/2003 | 7/23/2003 | A | PASS |
Alan Hauser
|
|
|
Finaled by inspector at 7/23/2003 7:59:37 PM
|
Final | 7/22/2003 | 7/23/2003 | 7/23/2003 | A | PASS |
Alan Hauser
|
|
|
Scheduled by a contractor via Hello! on 7/22/2003 at 10:07:44 PM. Contact: ###-####.
|
Final | 7/21/2003 | 7/22/2003 | 7/22/2003 | A | NR |
Alan Hauser
|
|
|
code requires full size flex, same as opening into appliance, and hvac hasn't finished vent to water heater 7/22/2003 8:02:58 PM
|
Pressure Test | 7/3/2003 | 7/3/2003 | 7/3/2003 | P | PASS |
Alan Hauser
|
|
|
kirk; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
Pressure Test | 7/2/2003 | 7/2/2003 | 7/2/2003 | P | FAIL |
Alan Hauser
|
|
|
pressure has dropped on test 7/3/2003 1:04:18 AM
|
Pressure Test | 5/30/2003 | 5/30/2003 | 5/30/2003 | P | FAIL |
Alan Hauser
|
|
|
RTU'S are larger in btu size than shown on plan, need to recheck pipe sizing to see if will work 5/30/2003 11:33:51 PM
|
Application received | | | 5/29/2003 | | |
|
|
|
|
Issue & PRINT permit | | | 5/29/2003 | | DONE |
|
|
|
|