Second Notice MEC | 7/7/2004 | 7/7/2004 | 7/12/2004 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 6/21/2004 | 7/7/2004 | | DONE |
|
|
|
|
DOC - Permit Finaled | 6/21/2004 | 6/21/2004 | 6/21/2004 | A | PASS |
Dixie Fellows
|
|
|
Finaled by inspector at 6/21/2004 10:09:02 AM
|
Final | 6/21/2004 | 6/21/2004 | 6/21/2004 | A | PASS |
Dixie Fellows
|
|
|
per Dixie.
|
Final | 6/17/2004 | 6/18/2004 | 6/18/2004 | A | FAIL |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: Sonja Hankel w/h calls for 20" clearance at top to combustible...these have 14"...unable to find venting specs for w/h 6/18/2004 10:53:08 AM
|
MEC-Aging Inspection | 6/15/2004 | 6/15/2004 | 6/15/2004 | | PASS |
Dixie Fellows
|
|
|
work in progress 6/16/2004 2:26:46 PM
|
Pressure Test | 4/12/2004 | 4/12/2004 | 4/12/2004 | P | FAIL |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: Sonja Hankel need 30lb guage for a low pressure test 4/12/2004 2:52:09 PM
|
Pressure Test | 4/8/2004 | 4/8/2004 | 4/8/2004 | P | FAIL |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: Sonja Hankel pipe buried..wrong guage or wrong test not sure..the installer wont be back until monday...called sonja and she will reschedule 4/8/2004 1:34:22 PM
|
Pressure Test | 2/18/2004 | 2/18/2004 | 2/18/2004 | P | PART |
Dixie Fellows
|
|
|
de best- ###-####....###-#### 2/18/2004 3:18:17 PM 60lb test to line in bldg ok...waiting on outside line to ahu 2/18/2004 3:18:46 PM
|
Application received | | | 2/18/2004 | | |
|
|
|
|
Issue & PRINT permit | | | 2/18/2004 | | DONE |
|
|
|
|
Owner Supplied Equipment | 2/18/2004 | | | | |
|
|
|
|