Third Notice MEC | 2/7/2005 | 2/7/2005 | 3/11/2005 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice MEC | 1/28/2005 | 1/28/2005 | 2/7/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 1/18/2005 | 1/28/2005 | | DONE |
|
|
|
|
DOC - Permit Finaled | 1/18/2005 | 1/18/2005 | 1/18/2005 | P | PASS |
Troy James
|
|
|
Finaled by inspector at 1/18/2005 12:13:46 PM
|
Final | 1/14/2005 | 1/18/2005 | 1/18/2005 | A | PASS |
Troy James
|
|
|
rich or jr ###-####; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Conference | 1/12/2005 | 1/13/2005 | 1/13/2005 | A | DONE |
Troy James
|
|
|
9:00 am 9:00 am discussed grease duct installation requirements at roof 1/13/2005 9:16:49 AM
|
Final | 1/7/2005 | 1/7/2005 | 1/7/2005 | P | FAIL |
Troy James
|
|
|
jr Note: exhaust hood; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
grease exhaust to close to parapet wall, need fire wrap where penetrate roof, grease duct at exhaust fan has no slope to duct, air balance does not meet required design per code. 1/7/2005 4:00:10 PM
|
Rough-in | 11/30/2004 | 11/30/2004 | 11/30/2004 | P | PART |
Dixie Fellows
|
|
|
Andy; Phone #: ###-#### Internet Inspection Request from: Jan Rice welds in duct ok 11/30/2004 3:14:47 PM
|
Application received | | | 11/22/2004 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 11/22/2004 | | DONE |
|
|
|
|