Final | 6/9/2005 | 6/10/2005 | 6/10/2005 | P | PASS |
Troy James
|
|
|
rick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Final | 6/7/2005 | 6/7/2005 | 6/7/2005 | P | FAIL |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rick Stockman...filter access door to be accessible without removing flues
|
Rough-in | 5/9/2005 | 5/10/2005 | 5/10/2005 | A | PASS |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: Matt Hansen pressure test ok and R/I
|
Rough-in | 5/5/2005 | 5/9/2005 | 5/9/2005 | A | FAIL |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: Matt Hansen pressure test failed, no test on guage, provide seperate chase for b-vent, not allowed in open return plenum
|
Rough-in | 5/5/2005 | 5/6/2005 | 5/5/2005 | P | CANC |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: Matt Hansen Inspection cancelled from web by: Matt Hansen
|
Application received | | | 4/12/2005 | | |
|
|
|
|
Issue permit | | | 4/12/2005 | | DONE |
|
|
|
|