Final | 1/12/2006 | 1/13/2006 | 1/13/2006 | A | PASS |
Troy James
|
|
|
Per Dixie - need to reschedule for AM Friday 1/13.; Phone #: ###-#### x202 Internet Inspection Request from: Patti Forsythe
|
Final | 1/10/2006 | 1/11/2006 | 1/11/2006 | P | PEND |
Dixie Fellows
|
|
|
Please call Patti re: access; Phone #: ###-#### x202 Internet Inspection Request from: Patti Forsythe...out of time..i called patti to reschedule
|
Rough-in | 8/23/2005 | 8/23/2005 | 8/23/2005 | A | PASS |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jennifer Jenson
|
Rough-in | 8/22/2005 | 8/22/2005 | 8/22/2005 | P | FAIL |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jennifer Jenson talked to contractor to provide combustion air and clearance to b-vent and framer to build platform to inline exhaust fan in attic and to revise permit to show the correct amount of fans and fireplaces installed
|
Pressure Test | 8/19/2005 | 8/23/2005 | 8/22/2005 | A | CANC |
Dixie Fellows
|
|
|
Re-Inspect; Phone #: ###-#### Internet Inspection Request from: Jennifer Jenson Inspection cancelled from web by: Jennifer Jenson
|
Rough-in | 8/19/2005 | 8/23/2005 | 8/22/2005 | A | CANC |
Dixie Fellows
|
|
|
Re-inspect; Phone #: ###-#### Internet Inspection Request from: Jennifer Jenson Inspection cancelled from web by: Jennifer Jenson
|
Rough-in | 8/18/2005 | 8/19/2005 | 8/19/2005 | A | FAIL |
Bill VanDegrift
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jennifer Jenson provide 1" clearance on both fire place flues. provide clearance and hang water heater B-vent. seal kitchen exhaust duct. update fixture count on permit. seal return air duct by furnace. use metal duct for makeup air to mech room. called their office with the last correction because I forgot to include it on the correction notice.
|
Pressure Test | 8/18/2005 | 8/19/2005 | 8/19/2005 | A | PASS |
Bill VanDegrift
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jennifer Jenson gas test ok
|
Pressure Test | 7/26/2005 | 7/27/2005 | 7/27/2005 | A | NR |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jennifer Jenson
|
Rough-in | 7/26/2005 | 7/27/2005 | 7/27/2005 | A | NR |
Dixie Fellows
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jennifer Jenson..call for conference
|
Application received | | | 6/24/2005 | | DONE |
|
|
|
This permit was created on the web by Jennifer Jenson
|