Second Notice MEC | 12/28/2005 | 12/28/2005 | 12/29/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 12/1/2005 | 12/1/2005 | 12/28/2005 | | DONE |
Troy James
|
|
|
|
Final | 11/29/2005 | 11/30/2005 | 12/1/2005 | P | PASS |
Troy James
|
|
|
Scheduled by a contractor via Hello! on 11/29/2005 at 3:23:13 PM. Contact: ###-####.
|
Final | 11/29/2005 | 11/29/2005 | 11/29/2005 | A | FAIL |
Troy James
|
|
|
plumbing vents 10' away from outside air intake of rtu, condensate traps on rtu's and install shut off valve before gas regulator to unit heater
|
Pressure Test | 11/1/2005 | 11/1/2005 | 11/1/2005 | P | PASS |
Troy James
|
|
|
Scheduled by a contractor via Hello! on 11/1/2005 at 9:28:45 AM. Contact: ###-####.
|
Pressure Test | 10/24/2005 | 10/24/2005 | 10/24/2005 | P | FAIL |
Troy James
|
|
|
Scheduled by a contractor via Hello! on 10/24/2005 at 7:38:22 AM. Contact: ###-####. need 60 lb test min.
|
Pressure Test | 10/18/2005 | 10/19/2005 | 10/19/2005 | A | FAIL |
Troy James
|
|
|
Scheduled by a contractor via Hello! on 10/18/2005 at 2:28:19 PM. Contact: ###-####. bad guage
|
Application received | | | 8/11/2005 | | |
|
|
|
|
Issue permit | | | 8/11/2005 | | DONE |
|
|
|
|