Permit Information
Permit NumberMEC05-02841
StatusFinaled
Name TML INC
Site Address 950 W BANNOCK ST
Project Name10TH & BANNOCK
Customer Number 
ePlanReview 
Description
(Shell & Core) Air Handler on each floor HVAC per plans initial certificate of value $783,468.00 ///Final value is $830,668//4/14/06 LEG ///Revised final cert of value $838,396//8/16/06 LEG
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice 6/21/20066/21/2006 DONE
Second Notice MEC4/11/20064/11/20064/14/2006 DONE
First Notice has not been responded to.
First Notice3/28/20063/28/20064/11/2006 DONE
DetailsTroy James
Conference3/27/20063/28/20063/28/2006APASS
DetailsTroy James
met with Dixie to show her the job, she will take over TI's
Conference3/28/20063/28/20063/28/2006PPASS
DetailsDixie Fellows
meet troy at 1:30...met with troy to look over job, as i will be taking over the inspections for the ti"s
Final3/28/20063/28/20063/28/2006PPASS
DetailsTroy James
Final3/28/20063/28/20063/28/2006APEND
DetailsDixie Fellows
See Stan Lillquist with TML; Phone #: ###-#### Internet Inspection Request from: Dan Flaherty..this was troys final
Conference3/27/20063/27/20063/28/2006ADEFR
DetailsDixie Fellows
scheduled for tues am
Conference3/21/20063/22/20063/22/2006APASS
DetailsTroy James
meeting at 9:00 am, 225 9th st suite 610
Rough-in3/20/20063/20/20063/20/2006PPASS
DetailsTroy James
Scheduled by a contractor via Hello! on 3/20/2006 at 9:59:05 AM. Contact: ###-####. core and shell ok for temp
Rough-in3/13/20063/14/20063/14/2006AFAIL
DetailsTroy James
Scheduled by a contractor via Hello! on 3/13/2006 at 3:20:31 PM. Contact: ###-####. need to verify fire damper required at intermediate floor transfer air and combustion air at penthouse and fire dampers at floor penetrations in some instances need to be verified. ok fire dampers at floors 6 and 7 at shaft and all air handler units ok
Rough-in2/28/20062/28/20062/28/2006PPASS
DetailsTroy James
Scheduled by a contractor via Hello! on 2/28/2006 at 8:17:18 AM. Contact: ###-####. f/d and rough ok at restrooms to floors 2 through 5
Rough-in2/22/20062/23/20062/23/2006AFAIL
DetailsTroy James
dan ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
fsd still installed incorrectly at shaft wall
Override - Parcel Holds1/1/19001/1/19002/22/2006  
need mec insp
Rough-in2/6/20062/7/20062/10/2006AFAIL
DetailsTroy James
Scheduled by a contractor via Hello! on 2/6/2006 at 2:30:59 PM. Contact: ###-####. need angles on all four sides of f/d at shaft with screws every 8" screwed into shaft
Rough-in1/10/20061/11/20061/11/2006APART
DetailsDixie Fellows
Scheduled by a contractor via Hello! on 1/10/2006 at 2:47:34 PM. Contact: ###-####....1st floor bathrooms ok
Rough-in12/29/200512/30/200512/30/2005APART
DetailsDixie Fellows
stan ###-####...shaft on 7-9th floors ok
Rough-in12/29/200512/29/200512/29/2005PPEND
DetailsDixie Fellows
Scheduled by a contractor via Hello! on 12/29/2005 at 10:23:26 AM. Contact: ###-####....i rescheduled this for fri am..i will meet stan at 8:30
Rough-in12/8/200512/9/200512/9/2005APART
DetailsDixie Fellows
Scheduled by a contractor via Hello! on 12/8/2005 at 2:11:58 PM. Contact: ###-####...looked at s/f dampers at shaft
Rough-in11/16/200511/17/200511/17/2005APART
DetailsDixie Fellows
Scheduled by a contractor via Hello! on 11/16/2005 at 3:56:11 PM. Contact: ###-####...ok to cover exhaust shafts
Application received  9/2/2005  
Issue & PRINT permit  9/2/2005 DONE