Final | 2/27/2008 | 2/28/2008 | 2/28/2008 | A | PASS |
Bill VanDegrift
|
|
|
dwanyne Phone #: ###-#### final ok with future ac coil condensate port plugged.
|
Final | 2/26/2008 | 2/27/2008 | 2/27/2008 | A | NH |
Dixie Fellows
|
|
|
les Phone #: ###-####
|
Rough-in | 12/7/2007 | 12/7/2007 | 12/7/2007 | P | PASS |
Lee Rice
|
|
|
dewayne Phone #: ###-####
|
Rough-in | 12/6/2007 | 12/6/2007 | 12/6/2007 | P | FAIL |
Bill VanDegrift
|
|
|
dewayne Phone #: ###-#### b-vent prohibited in return air plenum. insulation shield required on b-vent in attic. insulate return air box in attic. combustion air is undersized. 20# test ok
|
Application received | | | 12/6/2007 | | |
|
|
|
|
Issue permit | | | 12/6/2007 | | DONE |
|
|
|
|