Second Notice MEC | 6/25/2008 | 6/25/2008 | 7/11/2008 | | DONE |
Tisha Gallop
|
|
|
This permit finaled on the web by Jeff Miranda
|
First Notice | 6/6/2008 | 6/6/2008 | 6/25/2008 | | DONE |
Troy James
|
|
|
|
Final | 6/6/2008 | 6/6/2008 | 6/6/2008 | P | PASS |
Troy James
|
|
|
|
Final | 6/5/2008 | 6/5/2008 | 6/5/2008 | P | FAIL |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jeff Miranda piping for gas regulator venting is still not supported as requested from previous correction to installer
|
Reinspection Fee (no hold) | 6/5/2008 | 6/5/2008 | 6/5/2008 | P | DONE |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jeff Miranda piping for gas regulator vent still is not supported as requested on june 3rd inspection
|
Conference | 6/3/2008 | 6/4/2008 | 6/4/2008 | P | NR |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jeff Miranda
|
Final | 6/3/2008 | 6/3/2008 | 6/3/2008 | P | FAIL |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jeff Miranda went over problems with contractor on previous c/n
|
Final | 5/30/2008 | 6/2/2008 | 6/2/2008 | A | FAIL |
Troy James
|
|
|
please sign off on the job sheet with the superintendent. Radix (Keil) Phone #: ###-#### Internet Inspection Request from: Jeff Miranda gas regulators need to vent 10' away or 3' above fresh air intake, label gas line at meters
|
Pressure Test | 5/22/2008 | 5/22/2008 | 5/22/2008 | P | PASS |
Troy James
|
|
|
Ready for inspection after 2:00 pm. Phone #: ###-#### Internet Inspection Request from: Jeff Miranda 60# test for 10 gas lines
|
Application received | | | 3/10/2008 | | DONE |
|
|
|
This permit was created on the web by Jeff Miranda
|