First Notice | 9/11/2009 | 9/11/2009 | 2/14/2012 | | DONE |
Troy James
|
|
|
This permit finaled on the web by AMANDA FARNSWORTH
|
Final | 9/11/2009 | 9/11/2009 | 9/11/2009 | A | PASS |
Troy James
|
|
|
|
Rough-in | 8/31/2009 | 8/31/2009 | 8/31/2009 | P | PASS |
Troy James
|
|
|
PLEASE CALL KYLE Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH ok to drop ceiling at maintenance building
|
Rough-in | 8/21/2009 | 8/21/2009 | 8/21/2009 | A | PASS |
Troy James
|
|
|
Please call Kyle Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH maintenance building
|
Rough-in | 8/11/2009 | 8/11/2009 | 8/11/2009 | P | PASS |
Troy James
|
|
|
Please call kyle Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH ok to cover hard lid to vehicle maintenance building
|
Rough-in | 8/7/2009 | 8/10/2009 | 8/10/2009 | A | FAIL |
Troy James
|
|
|
troy, told them to wait till monday, alan
unble to contact kyle and need to see approved plans
|
Rough-in | 8/6/2009 | 8/7/2009 | 8/10/2009 | P | CANC |
Troy James
|
|
|
Please call Kyle Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH
|
Rough-in | 8/5/2009 | 8/5/2009 | 8/6/2009 | P | PASS |
Troy James
|
|
|
Please call kyle Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH ok to cover offices attached to main building
|
Rough-in | 7/29/2009 | 7/30/2009 | 7/30/2009 | A | PASS |
Troy James
|
|
|
please call kyle Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH ok to cover ceiling main office area
|
Rough-in | 7/20/2009 | 7/21/2009 | 7/21/2009 | A | PART |
Troy James
|
|
|
please call Kyle Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH dry good storage and offices ok, need to fix fire damper at electrical room main office
|
Rough-in | 7/8/2009 | 7/9/2009 | 7/9/2009 | A | PART |
Troy James
|
|
|
please call kyle Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH humper building, pvc piping needs to be removed or insulated, ok to insulate ducts
|
Rough-in | 6/22/2009 | 6/22/2009 | 6/22/2009 | P | PASS |
Troy James
|
|
|
Kyle Clark Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH guard shack exhuast fan
|
Rough-in | 6/2/2009 | 6/2/2009 | 6/2/2009 | P | PART |
Dixie Fellows
|
|
|
please call kyle clark Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH...shower ok for lid
|
Rough-in | 6/1/2009 | 6/2/2009 | 6/2/2009 | A | PART |
Dixie Fellows
|
|
|
PLEASE CALL KYLE CLARK Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH..ok to cover hard lids in office restrooms..locker room..main restroom..need exhaust in shower room before cover..finish some insulating of ducts
|
Conference | 5/15/2009 | 5/18/2009 | 5/18/2009 | A | CANC |
Troy James
|
|
|
|
Rough-in | 5/15/2009 | 5/15/2009 | 5/15/2009 | P | PASS |
Troy James
|
|
|
PLEASE CALL KYLE CLARK Phone #: ###-#### Internet Inspection Request from: AMANDA FARNSWORTH ok to cover restroom north of forklift charging room
|
Rough-in | 5/12/2009 | 5/13/2009 | 5/14/2009 | A | FAIL |
Troy James
|
|
|
Phone #: ###-#### Internet Inspection Request from: RaChelle Meister waiting for general contractor to decide what they are going to do with the open plenum
|
Conference | 5/11/2009 | 5/12/2009 | 5/12/2009 | A | FAIL |
Troy James
|
|
|
walked job site with jim and forest
dry storage offices need return air plenum to be compliant with IMC for materials in plenum
|
Application received | | | 3/10/2009 | | DONE |
|
|
|
This permit was created on the web by AMANDA FARNSWORTH
|