Final | 7/28/2009 | 7/28/2009 | 7/28/2009 | P | PASS |
Troy James
|
|
|
oleg Phone #: ###-####
|
Final | 7/27/2009 | 7/27/2009 | 7/27/2009 | P | FAIL |
Troy James
|
|
|
Oleg-late afternoon please Phone #: ###-#### gas flex connector cannot be before regulator ar dryer
|
Final | 7/21/2009 | 7/21/2009 | 7/21/2009 | P | FAIL |
Troy James
|
|
|
oleg-should be open Phone #: ###-#### need gas regulators for range and dryer
|
Rough-in | 5/1/2009 | 5/4/2009 | 5/4/2009 | A | PASS |
Bill VanDegrift
|
|
|
8am ri 60# test ok
|
Rough-in | 4/29/2009 | 4/29/2009 | 4/29/2009 | A | PART |
Bill VanDegrift
|
|
|
oleg ###-#### just needs the water heater closet taken care of after framing inspection
|
Rough-in | 4/27/2009 | 4/28/2009 | 4/28/2009 | P | FAIL |
Bill VanDegrift
|
|
|
oleg Phone #: ###-#### 60# TEST OK WATER HEATER CLOSET TOO SHALLOW, USE APPROVED STRIKER PLATES, CONDENSATE FOR 2ND FLOOR INCOMPLETE.
|
Rough-in | 4/23/2009 | 4/24/2009 | 4/24/2009 | P | FAIL |
Bill VanDegrift
|
|
|
Oleg- PT also Phone #: ###-#### gas piping undersized, 1/4" grade required on 2nd floor frunace exhaust, remove stress on gas piping to 2nd floor furnace. provide installation instructions for the water heater, use approved striker plates on the csst, install condensate piping for the basement furnace, seal joints in the range exhaust duct.
|
Pressure Test | 4/14/2009 | 4/14/2009 | 4/14/2009 | P | PART |
Dixie Fellows
|
|
|
Oleg Phone #: ###-####...20lb gas from garage to house ok
|
Pressure Test | 4/13/2009 | 4/13/2009 | 4/13/2009 | P | FAIL |
Dixie Fellows
|
|
|
Oleg Phone #: ###-####---back fill under gas line with dirt or sand...need btu load
|
Application received | | | 4/13/2009 | | |
|
|
|
|
Issue permit | | | 4/13/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|