First Notice | 8/21/2009 | 8/21/2009 | 12/3/2009 | | DONE |
Alan Hauser
|
|
|
This permit finaled on the web by Sonja Hankel
|
Final | 8/20/2009 | 8/21/2009 | 8/21/2009 | A | PASS |
Alan Hauser
|
|
|
|
Rough-in | 8/18/2009 | 8/18/2009 | 8/18/2009 | A | FAIL |
Troy James
|
|
|
need correct gas hoses to kitchen equipment, kitchen equipment do not fit under hood north side, general contractor to resolve this problem
|
Pressure Test | 8/12/2009 | 8/13/2009 | 8/13/2009 | A | PASS |
Alan Hauser
|
|
|
two 60# test to equipment over kitchen
|
Pressure Test | 7/9/2009 | 7/9/2009 | 7/9/2009 | P | CANC |
Alan Hauser
|
|
|
This is ready this morning. please call gary with questions ###-#### Phone #: ###-#### Internet Inspection Request from: Sonja Hankel Inspection cancelled from web by: Sonja Hankel
|
Pressure Test | 6/22/2009 | 6/23/2009 | 6/23/2009 | A | PART |
Alan Hauser
|
|
|
pressure test ok for three roof top units, 60#
|
Application received | | | 6/22/2009 | | DONE |
|
|
|
This permit was created on the web by Sonja Hankel
|