Final | 8/2/2010 | 8/2/2010 | 8/2/2010 | P | PASS |
Troy James
|
|
|
|
Final | 7/28/2010 | 7/29/2010 | 7/29/2010 | A | FAIL |
Troy James
|
|
|
Please do final. Any questions call Dale ###-#### Need access code call ###-#### Phone #: ###-#### >> Inspection requested via web by Diane Myslivy support for b-vent has to be ridid material when only using two support at same side of flue
|
Final | 7/27/2010 | 7/27/2010 | 7/27/2010 | P | FAIL |
Dixie Fellows
|
|
|
Dixie, contractor says that you approved relocation of flue for water heater. There are no notes stating such. I will let you complete final inspection on this job...B-VENT TO BE 2' HIGHER THAN VERTICAL WALL WITHIN 8'.
|
Final | 7/20/2010 | 7/26/2010 | 7/26/2010 | A | FAIL |
Troy James
|
|
|
Please do final if you need access please call the office for the code. Phone #: ###-#### >> Inspection requested via web by Diane Myslivy flue for water heater required to be 8' from adjacent wall and unable to access house, wood floors recently finished, incomplete inspection
|
Rough-in | 6/10/2010 | 6/11/2010 | 6/11/2010 | P | PASS |
Dixie Fellows
|
|
|
Please do rough in late afternoon, if you need access code please call ###-#### Inspection requested from web by: Lisa Whitney
|
Application received | | | 6/4/2010 | | DONE |
|
|
|
This permit was created on the web by Lisa Whitney
|