Mechanical Permit - Alteration: Provide and install HVAC equipment, grilles, registers, ductwork, insulation, controls, stainless steel backing. Install kitchen hoods and associated exhaust and supply fans.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice8/12/20108/12/20106/19/2015 DONE
DetailsDixie Fellows
This permit finaled on the web by Karl Hestekin
Final8/12/20108/12/20108/12/2010PPASS
DetailsDixie Fellows
ok per Dixie ///dld....job finaled...decorative f/p will be pulled under another permit
Final8/6/20108/9/20108/9/2010ANR
DetailsDixie Fellows
Phone #: ###-#### >> Inspection requested via web by Karl Hestekin
Final8/3/20108/4/20108/4/2010AFAIL
DetailsDixie Fellows
rescheduled for wed am..gas line undersized...f/p and hood not installed yet...all ductwork above hood to be noncombustible...air balance not done..need to check roof when equipment ready
Final8/2/20108/3/20108/3/2010APEND
DetailsDixie Fellows
Karl Hestekin Phone #: ###-#### >> Inspection requested via web by Karl Hestekin...rescheduled for wed am
Rough-in7/12/20107/12/20107/12/2010PPASS
DetailsDixie Fellows
Karl Hestekin Phone #: ###-#### >> Inspection requested via web by Karl Hestekin...2nd wrap ok
Rough-in7/9/20107/9/20107/9/2010APASS
DetailsTroy James
ok first layer of grease duct wrap in kitchen area
Rough-in7/7/20107/8/20107/8/2010APART
DetailsDixie Fellows
Grease Duct Welds Inspection requested from web by: Karl Hestekin Phone #: ###-####..pinholes all repaired..ok to cover with insulation
Rough-in7/6/20107/7/20107/7/2010AFAIL
DetailsDixie Fellows
grease duct weld inspection//Karl ###-####..fix holes in grease duct..sand down rough edges at top of hood..pan out all metal in r/a drops
Override - Parcel Holds7/6/20101/1/19007/6/2010  
rough in
Override - Parcel Holds  7/6/2010  
Rough-in6/16/20106/17/20106/17/2010PPART
DetailsDixie Fellows
roy - around 1:00 if possible please Phone #: ###-####...section of grease duct from curb down good for light test
Override - Parcel Holds6/16/20101/1/19006/16/2010  
mec
Application received  6/15/2010 DONE