Final | 6/20/2011 | 6/21/2011 | 6/21/2011 | A | PASS |
Troy James
|
|
|
meet John at 9:00am verified letter from engineer and air balance report for the existing hood
|
Final | 6/7/2011 | 6/8/2011 | 6/8/2011 | A | FAIL |
Dixie Fellows
|
|
|
Call Albert @ ###-#### if you have any issues with the installation/inspection. Phone #: ###-#### >> Inspection requested via web by Angie maguire...called albert he didn't have any idea what i was talking about...need letter from captive air
|
Rough-in | 5/26/2011 | 5/27/2011 | 5/27/2011 | A | PART |
Troy James
|
|
|
need cover inspection for t-bar. Please call Albert @###-#### Phone #: ###-#### >> Inspection requested via web by Angie maguire
ok to cover ceilings, checked hood specs and air balance report. Need letter from captive aire with equipment stated on letter stating the hood is designed for this equipment. Specs show 2500 cfm design exaust and air balance design shows 2300cfm. This is ok.
|
Rough-in | 4/11/2011 | 4/12/2011 | 4/12/2011 | A | PART |
Dixie Fellows
|
|
|
###-#### need a cover inspection...ok to cover hard lids...need verification from hood manuf or engineer that hood will exhaust new equipment being installed..will need an air balance at final
|
Rough-in | 4/11/2011 | 4/11/2011 | 4/11/2011 | P | PEND |
Dixie Fellows
|
|
|
would like cover inspection. Please call Jerry @ ###-#### if you have any installation issues Phone #: ###-#### >> Inspection requested via web by Angie maguire
|
Owner Supplied Equipment | | | 4/7/2011 | | |
|
|
|
|
Application received | | | 4/7/2011 | | DONE |
|
|
|
This permit was created on the web by Angie maguire
|