Final | 7/13/2011 | 7/14/2011 | 7/14/2011 | A | PASS |
Eric Strole
|
|
|
|
Final | 7/13/2011 | 7/13/2011 | 7/13/2011 | P | NR |
Eric Strole
|
|
|
|
Final | 7/12/2011 | 7/13/2011 | 7/13/2011 | A | FAIL |
Eric Strole
|
|
|
Please complete final inspection. Call Eric with any questions. Phone #: ###-#### >> Inspection requested via web by Alana Lane-no balance report
|
Final | 7/11/2011 | 7/12/2011 | 7/12/2011 | A | FAIL |
Eric Strole
|
|
|
Please complete final inspection. Call Eric with any questions Phone #: ###-#### >> Inspection requested via web by Alana Lane-need air balance report & manual j report on site.
|
Rough-in | 6/2/2011 | 6/3/2011 | 6/3/2011 | A | PASS |
Bill VanDegrift
|
|
|
please complete a reinspect call eric with any issues ###-#### Phone #: ###-#### >> Inspection requested via web by Alana Lane ri 20# test ductblaster ok pending acca report resubmittal approval.
|
Pressure Test | 6/1/2011 | 6/2/2011 | 6/2/2011 | A | PASS |
Bill VanDegrift
|
|
|
Call Eric @ ###-#### with any installation issues Phone #: ###-#### >> Inspection requested via web by Angie maguire 20# test ok
|
Rough-in | 6/1/2011 | 6/2/2011 | 6/2/2011 | A | FAIL |
Bill VanDegrift
|
|
|
Call Eric @ ###-#### with any installation issues Phone #: ###-#### >> Inspection requested via web by Angie maguire 2nd floor coil is smaller than design. windows dont match design. 2nd floor secondary drain connected to primary drain. duct blaster test ok 20# gas test ok
|
Application received | | | 5/12/2011 | | DONE |
|
|
|
This permit was created on the web by Alana Lane
|