Information based on query as of Friday, July 5, 2024.
Permit Information
Permit NumberMEC12-01152
StatusFinaled
Name AIR SOURCE HEATING & COOLING
Site Address 2907 N INNIS ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Mechanical Permit - Alteration: New ducting for remodel. 2 fans. Gas piping.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/7/20129/7/20129/7/2012PPASS
DetailsDixie Fellows
Phone #: ###-#### >> Inspection requested via web by Shaun Vogler
Rough-in5/10/20125/10/20125/10/2012APASS
DetailsDixie Fellows
duct blaster ok
Conference5/9/20125/9/20125/9/2012PFAIL
DetailsDixie Fellows
Duct blast scheduled for 1:30 pm with Matt from Momentum. Phone #: ###-#### >> Inspection requested via web by Shaun Vogler...this should have been a r/i
Rough-in5/9/20125/9/20125/9/2012PFAIL
DetailsDixie Fellows
air source...no manual J on site...no plans on site...no furnace set....i didn't accept the duct blaster test due to these corrections...re-call all when the job is READY
Pressure Test4/30/20124/30/20124/30/2012PPASS
DetailsTroy James
25# test
Rough-in4/30/20124/30/20124/30/2012PPASS
DetailsTroy James
Rough and pressure test. Phone #: ###-#### >> Inspection requested via web by Shaun Vogler
no duct blast test
Issue PAID IN FULL permit  4/16/2012 DONE
Payment received via Govolutions
Application received  4/16/2012 DONE
This permit was created on the web by Shaun Vogler