Final | 11/20/2012 | 11/21/2012 | 11/21/2012 | A | PASS |
Eric Strole
|
|
|
>> Inspection requested via web by Mike Almanza-Letter of approval for clearance of mantel legs from alpine fireplace is scanned in with the building permit. (clearance for mantel legs is not per manufacturer specs)
|
Final | 11/17/2012 | 11/19/2012 | 11/19/2012 | P | FAIL |
Bill VanDegrift
|
|
|
>> Inspection requested via web by Mike Almanza (1) provide listed clearances to side wall(6") and 1/2" to sheetrock at fireplace. see page 5 of installation instructions.
|
Final | 11/15/2012 | 11/15/2012 | 11/15/2012 | P | FAIL |
Eric Strole
|
|
|
>> Inspection requested via web by Mike Almanza-mantel legs need 6" to combustable material.
|
Final | 11/10/2012 | 11/13/2012 | 11/13/2012 | A | FAIL |
Eric Strole
|
|
|
>> Inspection requested via web by Mike Almanza-mantel and mantel leg clearance not per manufacture installation.
|
Rough-in | 9/12/2012 | 9/13/2012 | 9/13/2012 | A | PASS |
Bill VanDegrift
|
|
|
Phone #: ###-#### >> Inspection requested via web by Mike Almanza fp ri ok
|
Issue PAID IN FULL permit | | | 9/12/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/12/2012 | | DONE |
|
|
|
This permit was created on the web by Mike Almanza
|