Final | 6/26/2013 | 6/27/2013 | 6/27/2013 | A | PASS |
Bill VanDegrift
|
|
|
Call Greg with any questions Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN
|
Rough-in | 4/24/2013 | 4/25/2013 | 4/25/2013 | A | PASS |
Eric Strole
|
|
|
air care Phone #: ###-####-20 lb gas test and rough-in pass
|
Issue PAID IN FULL permit | | | 4/23/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Rough-in | 4/22/2013 | 4/23/2013 | 4/23/2013 | A | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN-need to install striker plates on csst per manufacture installation instructions. reinspection fee issued.
|
Rough-in | 4/22/2013 | 4/22/2013 | 4/22/2013 | P | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN-no change from last correction.
|
Rough-in | 4/20/2013 | 4/22/2013 | 4/22/2013 | A | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN-Need strike plates on gas tite in kitchen overhead.
|
Rough-in | 4/12/2013 | 4/12/2013 | 4/15/2013 | P | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN-1-Need to resubmit manual-j with all the duct sizing. 2-Ducts in crawlspace need straped to have 4" clearance above ground. 3-Need to install strike protection on gas tite. 4-Need to nailplate dryer vent. 5-2nd flr bath exhaust is not hooked-up.
|
Issue PAID IN FULL permit | | | 3/28/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/28/2013 | | DONE |
|
|
|
This permit was created on the web by GREGORY ANDERSEN
|