First Notice | 4/17/2014 | 4/17/2014 | 5/22/2014 | | DONE |
Chad Schwendiman
|
|
|
|
Final | 4/17/2014 | 4/17/2014 | 4/17/2014 | P | PASS |
Chad Schwendiman
|
|
|
Please call Carl with any questions, thank you Phone #: ###-#### >> Inspection requested via web by Rhonda Marcum
|
Final | 12/16/2013 | 12/17/2013 | 12/17/2013 | A | CANC |
Troy James
|
|
|
Please call Gary with any questions. Phone #: ###-#### >> Inspection requested via web by Rhonda Marcum have not completed clearance reduction to ceiling above hood
|
Final | 11/15/2013 | 11/15/2013 | 11/15/2013 | P | FAIL |
Troy James
|
|
|
Please call Carl with any questions. Thank you! Phone #: ###-#### >> Inspection requested via web by Rhonda Marcum Need to terminate exhaust fan above the parapet and need clearances rquired above hood. Need air balance report. Need 3/4" clearance from grease duct to combustible roof framing.
|
Final | 11/14/2013 | 11/14/2013 | 11/14/2013 | P | FAIL |
Dixie Fellows
|
|
|
THANK YOU! Phone #: ###-#### >> Inspection requested via web by Rhonda Marcum...need manuf specs for hood and fryer..need access to attic and roof..is wall behind fryer non-combustible?? where are we getting our requred make-up air?? do we need 18" clearance above hood to combustible?? where is our air blance report?? RESCHEDULE WHEN THESE ARE ADDRESSE!
|
Issue PAID IN FULL permit | | | 11/14/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/14/2013 | | DONE |
|
|
|
This permit was created on the web by Rhonda Marcum
|