Final | 5/6/2014 | 5/6/2014 | 5/6/2014 | A | PASS |
Chad Schwendiman
|
|
|
Garage code is 7550 for entry. Phone #: ###-#### >> Inspection requested via web by claude croy
|
Rough-in | 3/25/2014 | 3/25/2014 | 3/25/2014 | P | PASS |
Chad Schwendiman
|
|
|
>> Inspection requested via web by claude croy
|
Rough-in | 3/24/2014 | 3/25/2014 | 3/25/2014 | A | PART |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by claude croy - 20LB gas pressure pass, 5Lb flue pressure pass. Need 6" fresh air duct to return per manual J.
|
Rough-in | 3/24/2014 | 3/24/2014 | 3/24/2014 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by claude croy - Need APPROVED manual J on-site.
|
Rough-in | 3/20/2014 | 3/21/2014 | 3/21/2014 | A | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by claude croy - No manual j on site. need 1" clearance between water heater b-vent and insulation sheild. 5lb Flue pressure failed.
|
Issue PAID IN FULL permit | | | 3/18/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/18/2014 | | DONE |
|
|
|
This permit was created on the web by claude croy
|