Final | 7/18/2014 | 7/18/2014 | 7/18/2014 | P | PASS |
Chad Schwendiman
|
|
|
Final inspection. Northwest Heating left a ladder for the inspector to access the attic. John Kramis: ###-#### Phone #: ###-#### >> Inspection requested via web by Frank Marturello
|
Pressure Test | 7/18/2014 | 7/18/2014 | 7/18/2014 | P | PASS |
Chad Schwendiman
|
|
|
Re-inspection of the vent pipe pressure test. Phone #: ###-#### >> Inspection requested via web by Frank Marturello - 20LB GAS PRESSURE PASS, 5LB FLUE PRESSURE PASS
|
Rough-in | 6/27/2014 | 7/2/2014 | 7/2/2014 | A | PASS |
Chad Schwendiman
|
|
|
Contact Kristine: ###-#### Phone #: ###-#### >> Inspection requested via web by Frank Marturello -
|
Pressure Test | 7/2/2014 | 7/2/2014 | 7/2/2014 | P | FAIL |
Chad Schwendiman
|
|
|
Contact Kristine: ###-#### Phone #: ###-#### >> Inspection requested via web by Frank Marturello - 5LB FLUE PRESSURE FAIL, 20LB GAS PRESSURE PASS.
|
Rough-in | 5/12/2014 | 5/12/2014 | 5/12/2014 | P | PART |
Chad Schwendiman
|
|
|
Re-inspection of Rough In for cover. Jeff: ###-#### Phone #: ###-#### >> Inspection requested via web by Frank Marturello - NEW ADDITION PASS.
|
Rough-in | 5/9/2014 | 5/12/2014 | 5/12/2014 | A | FAIL |
Chad Schwendiman
|
|
|
Rough in for cover on new addition. Contact Jeff: ###-#### Phone #: ###-#### >> Inspection requested via web by Frank Marturello - NEED 12" RETURN TO MASTER BEDROOM PER APPROVED MANUAL J, NEED TO PROVIDE ACCESS OPENING IN CLOSET CEILING FOR EXHAUST FAN IN ATTIC
|
Issue PAID IN FULL permit | | | 4/29/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/29/2014 | | DONE |
|
|
|
This permit was created on the web by Frank Marturello
|