Final | 6/16/2014 | 6/16/2014 | 6/16/2014 | P | PASS |
Dixie Fellows
|
|
|
final ok
|
Final | 6/13/2014 | 6/16/2014 | 6/16/2014 | P | FAIL |
Dixie Fellows
|
|
|
Final Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..the dishwasher doesn't have the vapor attachment installed
|
Final | 6/12/2014 | 6/13/2014 | 6/12/2014 | P | NR |
Dixie Fellows
|
|
|
final Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..waiting on dishwasher
|
Final | 6/12/2014 | 6/12/2014 | 6/12/2014 | P | NR |
Dixie Fellows
|
|
|
Final - 3rd times a charm! Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..dishwasher not installed
|
Final | 6/10/2014 | 6/10/2014 | 6/11/2014 | P | FAIL |
Troy James
|
|
|
final Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen Need air balance report. Grease collector at the exhaust fans. Self condensing dishwasher or install type 2 hood. Plumber needs to install approved vent cap at gas regulator on roof and condensate trap to rtu's.
|
Rough-in | 5/30/2014 | 6/2/2014 | 6/2/2014 | A | PASS |
Dixie Fellows
|
|
|
rescheduled this inspection for you..fire barrier installed above hood from manuf ok
|
Rough-in | 5/30/2014 | 5/30/2014 | 5/30/2014 | A | CANC |
Troy James
|
|
|
Insulation on top of hood Phone #: ###-#### >> Inspection requested via web by David Tully rescheduled for monday for dixie to approve
|
Conference | 5/28/2014 | 5/29/2014 | 5/29/2014 | A | FAIL |
Dixie Fellows
|
|
|
Grease Duct Inspection Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..THIS SHOULD HAVE BEEN A R/I...RESCHEDULE FOR ONE
|
Rough-in | 5/21/2014 | 5/22/2014 | 5/22/2014 | A | PART |
Dixie Fellows
|
|
|
Hood inspection - upper
Grease duct light inspection on roof Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..light test for grease duct on roof ok
|
Rough-in | 5/20/2014 | 5/21/2014 | 5/21/2014 | A | PART |
Dixie Fellows
|
|
|
MEC-COM/RES INSPECTOR..ok to cover kitchen shaft
|
Rough-in | 5/19/2014 | 5/19/2014 | 5/19/2014 | P | PART |
Dixie Fellows
|
|
|
MAU ductwork inspection Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..ok..dont cover top of hood until i receive letter from manufacturer regarding damage done to fire barrier
|
Fees Due Hold | 5/17/2014 | | 5/19/2014 | | DONE |
|
|
|
|
Rough-in | 5/15/2014 | 5/16/2014 | 5/16/2014 | A | PART |
Dixie Fellows
|
|
|
firewrap inspection Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..bands on fire-wrap ok...need a stamped signed letter from captive-air engineering department regarding fix for tearing up the fire-barrier at top of hood that maintains "0" clearance listing
|
Rough-in | 5/15/2014 | 5/15/2014 | 5/15/2014 | P | FAIL |
Chad Schwendiman
|
|
|
firewrap inspection Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen - NEED TO ADD BANDS AROUND GREASE DUCT FIRE WRAP ON BOTTOM OF BOTH DUCTS.
|
Rough-in | 5/14/2014 | 5/14/2014 | 5/14/2014 | P | PART |
Dixie Fellows
|
|
|
grease duct inspection Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..all light test on grease duct ok
|
Rough-in | 5/13/2014 | 5/13/2014 | 5/13/2014 | P | FAIL |
Chad Schwendiman
|
|
|
light test - grease duct Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen - PIN HOLES IN BOTH GREASE DUCTS.
|
Rough-in | 5/12/2014 | 5/12/2014 | 5/12/2014 | P | FAIL |
Dixie Fellows
|
|
|
light test - grease duct Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..pin hole above hood..to light at 2nd floor to do the test
|
Rough-in | 5/8/2014 | 5/8/2014 | 5/8/2014 | P | PART |
Chad Schwendiman
|
|
|
cover inspection Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen - OK TO COVER SOFFITS IN BATHROOMS.
|
Rough-in | 5/7/2014 | 5/7/2014 | 5/7/2014 | P | PASS |
Troy James
|
|
|
light test at tvr shop ok light test for the two sections
|
Rough-in | 5/6/2014 | 5/7/2014 | 5/7/2014 | A | CANC |
Troy James
|
|
|
Light Test for Ductwork at TVR in the AM. Call Bob @###-#### Address: 2925 S. Cole Rd. Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen rescheduled for afternoon
|
Conference | 5/1/2014 | 5/1/2014 | 5/1/2014 | P | PASS |
Dixie Fellows
|
|
|
Grease hood courtesy inspection Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..DISCUSSED CLEARANCES AT TYPE 1 HOOD
|
Issue PAID IN FULL permit | | | 4/30/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/30/2014 | | DONE |
|
|
|
This permit was created on the web by Brandon Sorensen
|
First Notice | 6/16/2014 | 6/16/2014 | | | |
Dixie Fellows
|
|
|
|