Permit NumberMEC14-01651
StatusFinaled
Name TVR INC
Site Address 211 N 8TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Mechanical Permit - New: Provide and Install 2 each 3 ton RTUs with curbs and economizers for dining area and kitchen.
Reuse two existing RTUS and duct work including GRDS to serve existing dining areas
Relocate existing RTUS to meet current mechani
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/16/20146/16/20146/16/2014PPASS
DetailsDixie Fellows
final ok
Final6/13/20146/16/20146/16/2014PFAIL
DetailsDixie Fellows
Final Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..the dishwasher doesn't have the vapor attachment installed
Final6/12/20146/13/20146/12/2014PNR
DetailsDixie Fellows
final Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..waiting on dishwasher
Final6/12/20146/12/20146/12/2014PNR
DetailsDixie Fellows
Final - 3rd times a charm! Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..dishwasher not installed
Final6/10/20146/10/20146/11/2014PFAIL
DetailsTroy James
final Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen
Need air balance report. Grease collector at the exhaust fans. Self condensing dishwasher or install type 2 hood. Plumber needs to install approved vent cap at gas regulator on roof and condensate trap to rtu's.
Rough-in5/30/20146/2/20146/2/2014APASS
DetailsDixie Fellows
rescheduled this inspection for you..fire barrier installed above hood from manuf ok
Rough-in5/30/20145/30/20145/30/2014ACANC
DetailsTroy James
Insulation on top of hood Phone #: ###-#### >> Inspection requested via web by David Tully
rescheduled for monday for dixie to approve
Conference5/28/20145/29/20145/29/2014AFAIL
DetailsDixie Fellows
Grease Duct Inspection Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..THIS SHOULD HAVE BEEN A R/I...RESCHEDULE FOR ONE
Rough-in5/21/20145/22/20145/22/2014APART
DetailsDixie Fellows
Hood inspection - upper

Grease duct light inspection on roof Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..light test for grease duct on roof ok
Rough-in5/20/20145/21/20145/21/2014APART
DetailsDixie Fellows
MEC-COM/RES INSPECTOR..ok to cover kitchen shaft
Rough-in5/19/20145/19/20145/19/2014PPART
DetailsDixie Fellows
MAU ductwork inspection Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..ok..dont cover top of hood until i receive letter from manufacturer regarding damage done to fire barrier
Fees Due Hold5/17/2014 5/19/2014 DONE
Details
Rough-in5/15/20145/16/20145/16/2014APART
DetailsDixie Fellows
firewrap inspection Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..bands on fire-wrap ok...need a stamped signed letter from captive-air engineering department regarding fix for tearing up the fire-barrier at top of hood that maintains "0" clearance listing
Rough-in5/15/20145/15/20145/15/2014PFAIL
DetailsChad Schwendiman
firewrap inspection Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen - NEED TO ADD BANDS AROUND GREASE DUCT FIRE WRAP ON BOTTOM OF BOTH DUCTS.
Rough-in5/14/20145/14/20145/14/2014PPART
DetailsDixie Fellows
grease duct inspection Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..all light test on grease duct ok
Rough-in5/13/20145/13/20145/13/2014PFAIL
DetailsChad Schwendiman
light test - grease duct Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen - PIN HOLES IN BOTH GREASE DUCTS.
Rough-in5/12/20145/12/20145/12/2014PFAIL
DetailsDixie Fellows
light test - grease duct Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..pin hole above hood..to light at 2nd floor to do the test
Rough-in5/8/20145/8/20145/8/2014PPART
DetailsChad Schwendiman
cover inspection
Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen - OK TO COVER SOFFITS IN BATHROOMS.
Rough-in5/7/20145/7/20145/7/2014PPASS
DetailsTroy James
light test at tvr shop
ok light test for the two sections
Rough-in5/6/20145/7/20145/7/2014ACANC
DetailsTroy James
Light Test for Ductwork at TVR in the AM. Call Bob @###-#### Address: 2925 S. Cole Rd. Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen
rescheduled for afternoon
Conference5/1/20145/1/20145/1/2014PPASS
DetailsDixie Fellows
Grease hood courtesy inspection
Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen..DISCUSSED CLEARANCES AT TYPE 1 HOOD
Issue PAID IN FULL permit  4/30/2014 DONE
Payment received via Govolutions
Application received  4/30/2014 DONE
This permit was created on the web by Brandon Sorensen
First Notice6/16/20146/16/2014   
DetailsDixie Fellows