Final | 8/12/2014 | 8/13/2014 | 8/13/2014 | A | PASS |
Chad Schwendiman
|
|
|
garage code is 1234 Phone #: ###-#### >> Inspection requested via web by Krista Boss
|
Final | 8/7/2014 | 8/8/2014 | 8/8/2014 | A | FAIL |
Chad Schwendiman
|
|
|
garage code is 1234 and enter Phone #: ###-#### >> Inspection requested via web by Krista Boss - No air balance report on site.
|
Rough-in | 6/27/2014 | 6/30/2014 | 6/30/2014 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss
|
Rough-in | 6/26/2014 | 6/27/2014 | 6/27/2014 | A | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss - Need 6" fresh air to return. 4" installed. Need to install butterfly damper on fresh air duct at connection to return air can. Need 1" clearance to combustables on furnace (support linest away from b-vent). Need 1" clearance between b-vent and insulation shield on water heater.
|
Pressure Test | 6/26/2014 | 6/27/2014 | 6/27/2014 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss - 20lb gas pressure pass
|
Issue PAID IN FULL permit | | | 6/24/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/24/2014 | | DONE |
|
|
|
This permit was created on the web by Krista Boss
|