Final | 9/19/2014 | 9/19/2014 | 9/19/2014 | P | PASS |
Alan Hauser
|
|
|
|
Final | 9/18/2014 | 9/19/2014 | 9/19/2014 | A | PASS |
Alan Hauser
|
|
|
|
Final | 9/19/2014 | 9/19/2014 | 9/19/2014 | A | FAIL |
Troy James
|
|
|
Re-entering activity from 9-18-14 inspection. Stopped by later in day and door was open. I able to complete inspection. Need quick disconnect gas line to range and the cable connected from wall to range to restrict the range from pulling behond the flexible gas line capacity. Not sure whether this permit can be finaled at this time. Another permit is being reviewed for the installation of type 2 hood over range. No occupancy until hood is installed and approved. Also the system needs to be balanced. Outside air is still closed. Need 150 cfm per design.
|
Final | 9/17/2014 | 9/18/2014 | 9/18/2014 | A | FAIL |
Troy James
|
|
|
Phone #: ###-#### >> Inspection requested via web by Dustin Rich no access
|
Pressure Test | 8/15/2014 | 8/15/2014 | 8/15/2014 | A | PASS |
Bill VanDegrift
|
|
|
Inspection requested via web by Dustin Rich ri ok 20# gas test ok 5# flue test ok
|
Rough-in | 8/15/2014 | 8/15/2014 | 8/15/2014 | A | PASS |
Bill VanDegrift
|
|
|
Inspection requested via web by Dustin Rich ri ok
|
Rough-in | 8/14/2014 | 8/14/2014 | 8/14/2014 | P | NR |
Alan Hauser
|
|
|
|
Issue PAID IN FULL permit | | | 8/5/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/5/2014 | | DONE |
|
|
|
This permit was created on the web by Dustin Rich
|
First Notice | 9/19/2014 | 9/19/2014 | | | |
Alan Hauser
|
|
|
|
First Notice | 9/19/2014 | 9/19/2014 | | | |
Alan Hauser
|
|
|
|