Final | 10/6/2014 | 10/7/2014 | 10/7/2014 | P | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey
|
Conference | 8/15/2014 | 8/15/2014 | 8/15/2014 | P | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Aaron Toomey Inspection cancelled from web by: Aaron Toomey
|
Pressure Test | 8/14/2014 | 8/15/2014 | 8/15/2014 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Aaron Toomey - 20LB GAS PRESSURE PASS, 5LB FLUE PRESSURE PASS
|
Rough-in | 8/14/2014 | 8/15/2014 | 8/15/2014 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Aaron Toomey
|
Issue PAID IN FULL permit | | | 8/8/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/7/2014 | | DONE |
|
|
|
This permit was created on the web by Aaron Toomey
|