Final | 3/11/2015 | 3/11/2015 | 3/11/2015 | P | PASS |
Dixie Fellows
|
|
|
ted ###-####
|
Conference | 3/11/2015 | 3/11/2015 | 3/11/2015 | P | PASS |
Dixie Fellows
|
|
|
Sorry Dixie I clicked on the wrong house and I had already set it up before we changed it to 1:00. But we are straight. See you at 1:00 today Phone #: ###-#### >> Inspection requested via web by Jennifer Roy..corrections now done
|
Final | 3/6/2015 | 3/6/2015 | 3/6/2015 | P | FAIL |
Dixie Fellows
|
|
|
Please call with any questions or concerns.. Thank you Phone #: ###-#### >> Inspection requested via web by Jennifer Roy..SAME C/N AS LAST FRIDAY.
|
Final | 2/25/2015 | 2/25/2015 | 2/25/2015 | A | FAIL |
Dixie Fellows
|
|
|
Please call with any questions or concerns. Thank you. Phone #: ###-#### >> Inspection requested via web by Jennifer Roy..need to add 3 furn to permit..venting on w/h not done..location of outside air for kitchen hood. need locations for intakes and exhaust for furn and w/h in basement. there is an exhaust blowing directly on a/c that needs to be fixed. it would be great if the installer could meet me on this job to go over all this
|
Pressure Test | 10/3/2014 | 10/3/2014 | 10/3/2014 | P | PASS |
Dixie Fellows
|
|
|
1:00 duct blaster test. Please call with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Jennifer Roy..60lb gas ok..flue tests ok
|
Rough-in | 10/3/2014 | 10/3/2014 | 10/3/2014 | P | PASS |
Dixie Fellows
|
|
|
1:00 duct blaster test. Please call with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Jennifer Roy..r/i ok..duct blast ok
|
Issue PAID IN FULL permit | | | 9/11/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/11/2014 | | DONE |
|
|
|
This permit was created on the web by Jennifer Roy
|