Final | 11/17/2014 | 11/20/2014 | 11/20/2014 | A | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey
|
Pressure Test | 10/1/2014 | 10/2/2014 | 10/2/2014 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey - 5lb flue pass
|
Rough-in | 10/1/2014 | 10/2/2014 | 10/2/2014 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey
|
Pressure Test | 9/30/2014 | 10/1/2014 | 10/1/2014 | A | PART |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey - 5lb flue fail, 20lb gas pass
|
Rough-in | 9/30/2014 | 10/1/2014 | 10/1/2014 | A | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey - 6" fresh air duct needs to tie in to the return air plenum, need to use r-6 flex in the garage over build.
|
Issue PAID IN FULL permit | | | 9/19/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/19/2014 | | DONE |
|
|
|
This permit was created on the web by Aaron Toomey
|