Final | 3/30/2015 | 3/30/2015 | 3/30/2015 | P | PASS |
Chad Schwendiman
|
|
|
Economizer has been installed
|
Final | 3/24/2015 | 3/25/2015 | 3/25/2015 | A | FAIL |
Chad Schwendiman
|
|
|
fresh air hoods are now installed Inspection requested via web by Dustin Rich - still need to install economizer.
|
Final | 11/10/2014 | 11/12/2014 | 11/12/2014 | A | FAIL |
Chad Schwendiman
|
|
|
bottom lock box 0784 Phone #: ###-#### Inspection requested via web by Dustin Rich - Need economizers on roof top units per IECC C403.3.1
|
Final | 11/4/2014 | 11/7/2014 | 11/7/2014 | P | FAIL |
Chad Schwendiman
|
|
|
installer jarod ###-#### Inspection requested via web by Dustin Rich - need freash air hoods and economizers on roof top units
|
Issue PAID IN FULL permit | | | 10/8/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/8/2014 | | DONE |
|
|
|
This permit was created on the web by Dustin Rich
|
First Notice | 3/30/2015 | 3/30/2015 | | | |
Chad Schwendiman
|
|
|
|