Permit Information
Permit NumberMEC15-00101
StatusFinaled
Name YMC INC
Site Address 1105 S LA POINTE ST
Project NameWest Sherwood Apartments
Customer Number 
ePlanReviewNo
Description
Building 1
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/16/20157/16/20157/16/2015PPASS
DetailsChad Schwendiman
Final on all floors, please call Bryan. Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
Final7/14/20157/14/20157/14/2015PFAIL
DetailsChad Schwendiman
Final all floors and corridors (except clubhouse and parking garage), please call Bryan. Thank You! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - primary condensate drains need to be trapped per manufactures specs, supports for condensate drains are falling off the walls
Rough-in6/17/20156/17/20156/17/2015PPASS
DetailsChad Schwendiman
R/I for the clubhouse please, call Bryan. Thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - okay to cover hard lids in the club house area. okay to cover grid ceilings in the corridoors on all floors
Conference6/12/20156/12/20156/12/2015ADONE
DetailsChad Schwendiman
Bryan ###-####
Rough-in4/9/20154/9/20154/9/2015PCANC
DetailsChad Schwendiman
R/I for ducting, call Bryan. Thank You! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
Rough-in3/26/20153/27/20153/27/2015APART
DetailsChad Schwendiman
Please call Bryan for specifics. Thank you!! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - 217, and 3rd floor area 1 okay to cover soffits and hard lids
Rough-in3/17/20153/18/20153/18/2015APART
DetailsChad Schwendiman
Rm 216 ; 217, please call Bryanb with questions. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum - okay to cover soffits on 2nd floor of area 1 except for room 217
Rough-in3/12/20153/13/20153/13/2015PPART
DetailsChad Schwendiman
Please call Bryan with any questions. Thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - okay to cover walls indwelling units, okay to cover soffits in the dwelling units in the west wing
Rough-in3/10/20153/10/20153/10/2015AFAIL
DetailsChad Schwendiman
fire damp corridor, ok to cover - Brian Phone #: ###-#### - fire damper angles installed incorrectly. need to install per manufactures instructions.
Rough-in2/23/20152/24/20152/24/2015APART
DetailsChad Schwendiman
Rough in to cover walls, call Bryan with any questions. Thank You! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - area 1, 2nd floor walls okay to cover.
Rough-in2/20/20152/23/20152/23/2015AFAIL
DetailsChad Schwendiman
Rough in to cover walls. Please call Bryan. Thank You! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Need to fur out 2x4 walls with dryer vents running in them.
Conference2/18/20152/18/20152/18/2015PDONE
DetailsChad Schwendiman
Rough-in2/16/20152/17/20152/17/2015APART
DetailsChad Schwendiman
Inspection for Fire Dampers. Please call Bryan. Thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - 2nd floor fire damper clearances okay
Rough-in2/4/20152/4/20152/4/2015PPART
DetailsChad Schwendiman
Call Bryan with any questions. Thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - okay to cover bottom if tgi's in living units in 2nd. through 4th. floors, except for interior corner units and club house area, and bike rooms
Issue PAID IN FULL permit  1/13/2015 DONE
Payment received via Govolutions
Application received  1/8/2015