Final | 6/30/2015 | 7/1/2015 | 7/1/2015 | A | PASS |
Eric Strole
|
|
|
Oleg Phone #: ###-####
|
Rough-in | 4/10/2015 | 4/13/2015 | 4/13/2015 | A | PASS |
Chad Schwendiman
|
|
|
Oleg Phone #: ###-####
|
Fees Due Hold | 4/11/2015 | | 4/13/2015 | | DONE |
|
|
|
|
Rough-in | 4/10/2015 | 4/10/2015 | 4/10/2015 | P | FAIL |
Chad Schwendiman
|
|
|
Oleg ###-#### - corrections not complete
|
Rough-in | 4/9/2015 | 4/10/2015 | 4/10/2015 | A | FAIL |
Chad Schwendiman
|
|
|
Oleg-late am Phone #: ###-#### - corrections not fixed
|
Fee Due (change status F) | | | 4/10/2015 | | DONE |
|
|
|
|
Rough-in | 4/9/2015 | 4/9/2015 | 4/9/2015 | P | FAIL |
Troy James
|
|
|
Early afternoon please - Oleg Phone #: ###-#### Need 8" outside air duct per the approved report.
|
Pressure Test | 4/9/2015 | 4/9/2015 | 4/9/2015 | P | PASS |
Troy James
|
|
|
Early afternoon please - Oleg Phone #: ###-#### 5 # test to pvc and 20# test to gas
|
Pressure Test | 4/7/2015 | 4/8/2015 | 4/8/2015 | A | FAIL |
Chad Schwendiman
|
|
|
Oleg Phone #: ###-#### - need to pressure test pvc flue
|
Rough-in | 4/7/2015 | 4/8/2015 | 4/8/2015 | A | FAIL |
Chad Schwendiman
|
|
|
Oleg Phone #: ###-#### - need approved manual j on site, can't pull fresh air from roof on bld permits issued after 1-1-2015, it needs to terminate on the side of the house.
|
Issue PAID IN FULL permit | | | 3/29/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/29/2015 | | DONE |
|
|
|
This permit was created on the web by Oleg Chervak
|