Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberMEC15-02331
StatusFinaled
Name A+ ENERGY MANAGEMENT
Site Address 1021 S LUSK ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Install make up air unit and ductwork.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice6/23/20156/23/20157/3/2015 DONE
DetailsTroy James
This permit finaled on the web by David Cole
Final6/22/20156/23/20156/23/2015APASS
DetailsTroy James
Please call Dave for access if needed. Phone #: ###-#### >> Inspection requested via web by David Cole
Final6/17/20156/22/20156/22/2015PFAIL
DetailsTroy James
Please call Dave for access 30 minutes ahead of arrival if needed. Phone #: ###-#### >> Inspection requested via web by David Cole
Need exterior vent cap for gas regulator at make up air unit. Sediment trap after valve and before regulator and test port downstream of regulator
Final6/13/20156/18/20156/17/2015ACANC
DetailsChad Schwendiman
Call Dave for access. ###-#### Phone #: ###-#### >> Inspection requested via web by David Cole Inspection cancelled from web by: David Cole
Final6/9/20156/10/20156/10/2015ANR
DetailsChad Schwendiman
Call Dave for access. ###-#### Phone #: ###-#### Inspection requested via web by David Cole - not ready for a final. I entered a rough in for this.
Pressure Test6/10/20156/10/20156/10/2015APASS
DetailsChad Schwendiman
Call Dave for access. ###-#### Phone #: ###-#### Inspection requested via web by David Cole - 60lb gas pass
Rough-in6/10/20156/10/20156/10/2015APASS
DetailsChad Schwendiman
Call Dave for access. ###-#### Phone #: ###-#### Inspection requested via web by David Cole
Issue PAID IN FULL permit  5/30/2015 DONE
Payment received via Govolutions
Application received  5/30/2015 DONE
This permit was created on the web by David Cole