DOC - Permit Finaled | 10/13/2015 | 10/13/2015 | 10/13/2015 | P | PASS |
Troy James
|
|
|
|
Final | 10/12/2015 | 10/13/2015 | 10/13/2015 | A | PASS |
Troy James
|
|
|
Please call for access if no one home - Kyle Phone #: ###-####
|
Final | 10/1/2015 | 10/2/2015 | 10/2/2015 | P | CANC |
Chad Schwendiman
|
|
|
Kyle Phone #: ###-####
|
Rough-in | 7/29/2015 | 7/30/2015 | 8/3/2015 | A | PASS |
Bill VanDegrift
|
|
|
ri 20# test ok
|
Rough-in | 7/28/2015 | 7/29/2015 | 7/29/2015 | A | NR |
Bill VanDegrift
|
|
|
Kyle Phone #: ###-#### will inspect in the am acca report ready to resubmit
|
Rough-in | 7/27/2015 | 7/28/2015 | 7/28/2015 | P | FAIL |
Bill VanDegrift
|
|
|
Kyle Phone #: ###-####
1) Butler heating needs a permit for the work they are doing, furnace, gas etc. 2) needs clearance to grade for the duct in crawlspace 3) complete ducting in crawl 4) resubmit acca report showing changes to equipment, etc 5) 20# TEST OK
|
Rough-in | 7/22/2015 | 7/23/2015 | 7/23/2015 | P | FAIL |
Chad Schwendiman
|
|
|
Kyle Phone #: ###-#### 1) Need to rough in the range vent. 2)Hvac ducting needs to be sized and ran per the approved manual J 3) Need to install supply, and return plenum at furnace location 4) Need to install 6" fresh air duct to return plenum 5) Need return transfers out of bedrooms 6) Dryer duct can't have any screws in it 7) Need to rough in the line set for the A/C
|
Application received | | | 7/17/2015 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/17/2015 | | DONE |
|
|
|
|