Final | 4/22/2016 | 4/22/2016 | 4/22/2016 | P | PASS |
Chad Schwendiman
|
|
|
House will be open to have access to do final Phone #: ###-#### Inspection requested via web by Gary Reeves
|
Mec-Aging Inspection | 4/13/2016 | 4/13/2016 | 4/13/2016 | | CANC |
Chad Schwendiman
|
|
|
wip
|
Rough-in | 11/16/2015 | 11/17/2015 | 11/17/2015 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves
|
Rough-in | 11/13/2015 | 11/16/2015 | 11/16/2015 | P | FAIL |
Chad Schwendiman
|
|
|
PLEASE CALL ROBERT BEFORE TO INSPECTION Phone #: ###-#### Inspection requested via web by Gary Reeves - still need access to make-up air damper, still need nail plates on the dryer vent in the master suite
|
Pressure Test | 11/13/2015 | 11/16/2015 | 11/16/2015 | P | PASS |
Chad Schwendiman
|
|
|
PLEASE CALL ROBERT BEFORE TO INSPECTION Phone #: ###-#### Inspection requested via web by Gary Reeves - 60lb gas pass
|
Pressure Test | 11/12/2015 | 11/13/2015 | 11/13/2015 | P | CANC |
Chad Schwendiman
|
|
|
phone ###-#### Inspection cancelled from web by: Gary Reeves
|
Rough-in | 11/12/2015 | 11/13/2015 | 11/13/2015 | P | CANC |
Chad Schwendiman
|
|
|
phone ###-#### Inspection cancelled from web by: Gary Reeves
|
Pressure Test | 11/12/2015 | 11/12/2015 | 11/12/2015 | P | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
|
Rough-in | 11/12/2015 | 11/12/2015 | 11/12/2015 | P | CANC |
Chad Schwendiman
|
|
|
Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
|
Rough-in | 11/8/2015 | 11/9/2015 | 11/9/2015 | A | FAIL |
Chad Schwendiman
|
|
|
Can you please call robert as he would like to walk through with you, Phone #: ###-#### Inspection requested via web by Gary Reeves - corrections have not been made on the pizza oven from previous inspection, manual J doesn't match whats installed, missing nail plates on dryer vent, Need access to make up air damper for kitchen exhaust, need fresh air roughed in for furnaces, need combustion air roughed in for mechanical room in basement, need to complete the crawl.
|
Pressure Test | 11/8/2015 | 11/9/2015 | 11/9/2015 | A | PART |
Chad Schwendiman
|
|
|
Can you please call robert as he would like to walk through with you, Phone #: ###-#### Inspection requested via web by Gary Reeves - 20lb gas pass on all low pressure, 5lb flue pass on 3 furnace flues. 60lb gas fail, 5lb flue fail on water heater
|
Pressure Test | 10/12/2015 | 10/13/2015 | 10/13/2015 | A | FAIL |
Chad Schwendiman
|
|
|
need flue inspected for fire brick oven that will be hidden behind the upstairs furnace. Please call to set a time if you would like someone there to meet you. ###-#### Phone #: ###-#### Inspection requested via web by Gary Reeves - Need manufactors venting instructions for the brick oven, vent pipe requires 2" clearance to combustables, need 2" air gap between vent pipe and insulation shield.
|
Issue PAID IN FULL permit | | | 9/24/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/24/2015 | | DONE |
|
|
|
This permit was created on the web by Gary Reeves
|