Permit Information
Permit NumberMEC15-05385
StatusFinaled
Name CITY OF BOISE
Site Address 2108 S ATLANTIC ST
Project Name 
Customer Number 
ePlanReviewNo
Description
install variable refrgerat ductless heating/cooling units - 2 compressors and 5 evaporators. install energy recovery venterlator
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/22/201612/22/201612/22/2016PPASS
DetailsBrian Scoles
Final12/21/201612/21/201612/21/2016PFAIL
DetailsBrian Scoles
need combustion air in water heater closet- need 1" clearancve to combustibles to b vent on water heater flue- need foilmtape removed from b vent- need uv protection on line sets outdoors- need tp rodent proof penetrations exterior of building and seal off- left correction notice in closet by water heater
Mec-Aging Inspection12/16/201612/16/201612/16/2016 PEND
DetailsBrian Scoles
work in progress
Mec-Aging Inspection9/16/20169/16/20169/16/2016 PEND
DetailsBrian Scoles
Work in progress
Mec-Aging Inspection6/17/20166/17/20166/17/2016 CANC
DetailsChad Schwendiman
wip
Rough-in12/7/201512/7/201512/7/2015APART
DetailsTroy James
ok to cover line sets in walls
Application received  11/13/2015  
Issue FEE-WAIVED permit  11/13/2015 DONE