Permit Information
Permit NumberMEC16-00670
StatusFinaled
Name EVENFLO HEATING & AIR CONDITIONING
Site Address 509 E PARKCENTER BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Install new hvac
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice10/20/201610/20/201611/16/2016 DONE
DetailsChad Schwendiman
This permit finaled on the web by william kerwin
Final10/20/201610/20/201610/20/2016PPASS
DetailsChad Schwendiman
Final8/31/20168/31/20168/31/2016PPART
DetailsChad Schwendiman
Bj 5730755 Inspection requested via web by william kerwin - temporary occupancy okay, Still need to complete the condensate in units 309, 319, 223
Final8/31/20168/31/20168/31/2016AFAIL
DetailsChad Schwendiman
Bj 5730755 Inspection requested via web by william kerwin - still need to remove fire caulk from dampers in mechanical rooms per previous discussions
Final8/30/20168/30/20168/30/2016PPART
DetailsChad Schwendiman
bj###-#### Inspection requested via web by william kerwin - all units okay except for 110, 113, 212, 223, 225, 227, 303, 309, 311, 319, 324
Final8/26/20168/26/20168/26/2016PFAIL
DetailsChad Schwendiman
Call montessori on the trim please 9724667 Inspection requested via web by william kerwin - Need clamps on condensate tubing under sinks, need fire damper installed on fresh air duct to the corridoor mechanical rooms, need to finish ducting to corridoor units, need permanent ladder to access equipment on the roof
Conference8/16/20168/17/20168/17/2016ADONE
DetailsChad Schwendiman
Phone ###-####
Conference7/21/20167/21/20167/21/2016ADONE
DetailsChad Schwendiman
Phone ###-####
Conference4/25/20164/25/20164/25/2016ADONE
DetailsChad Schwendiman
Bj ###-#### - went over the approved drawings with Bj to address the condensate piping and exhaust fan location and duct work. They need to install per the approved drawing or provide documentation from the engineer showing that he approves of the changes
Rough-in4/22/20164/22/20164/22/2016APART
DetailsChad Schwendiman
Dropped ceilings. Bj 5730755. Thank You Inspection requested via web by william kerwin - okay to cover bathroom ceilings
Rough-in4/20/20164/20/20164/20/2016PFAIL
DetailsChad Schwendiman
Bj 5730755. Dropped ceiling inspection Inspection requested via web by william kerwin - Need to remove combustable material from with in the return air plenum
Rough-in4/19/20164/19/20164/19/2016PNR
DetailsChad Schwendiman
BJ ###-#### Inspection requested via web by william kerwin
Rough-in4/18/20164/18/20164/18/2016PNR
DetailsChad Schwendiman
Ductwork in drop ceilings. Late afternoon Inspection requested via web by william kerwin
Rough-in4/14/20164/14/20164/14/2016PPART
DetailsChad Schwendiman
Firedamper inspection Inspection requested via web by william kerwin - fire damper retaining angles okay on 1st, and 2nd floor
Rough-in4/8/20164/8/20164/8/2016PPART
DetailsChad Schwendiman
Phone ###-#### - retaining angle on supply plenum fire dampers okay in rooms 303, 306, 313, 315
Rough-in4/8/20164/8/20164/8/2016APART
DetailsChad Schwendiman
Late am. Firedamper inspection Inspection requested via web by william kerwin - retaining angles on fire dampers in supply plenums okay on the 3rd floor except for rooms 303, 306, 313,315
Rough-in3/30/20163/30/20163/30/2016PPART
DetailsChad Schwendiman
firedamper reinspect. THANKS CHAD! Appreciate your professionalism! Inspection requested via web by william kerwin - okay to cover bottom of tgi's and trusses in the bathrooms
Conference3/30/20163/30/20163/30/2016APASS
DetailsBen Livingston
Meet on site
Rough-in3/29/20163/30/20163/30/2016AFAIL
DetailsChad Schwendiman
firedamper inspection. Inspection requested via web by william kerwin - need to square up the plenum boxs and fire dampersnin some of the rooms
Conference3/28/20163/29/20163/29/2016ADONE
DetailsChad Schwendiman
Rob ###-#### meet to go over fire dampers - nmet to go over the fire damper installation in the supply plenums
Conference3/28/20163/28/20163/28/2016PCANC
DetailsChad Schwendiman
Rob ###-#### - rescheduled for tomorrow morning
Rough-in2/25/20162/25/20162/25/2016APART
DetailsChad Schwendiman
Call Rob Inspection requested via web by william kerwin - Okay to cover the dwelling units ceiling and walls on all three floors except for the bathroom ceilings on the 1st and 2nd floor where the supply plenum box is located. Okay to cover 3rd floor corridoors
Conference2/22/20162/23/20162/23/2016ADONE
DetailsChad Schwendiman
Inspection requested via web by william kerwin - I recevied the listings for the southwark dampers at the grill locations. The greenheck dampers are not listed for the application on the supply plenums. Need to install a damper that is listed for the application
Fees Due Hold2/18/2016 2/22/2016 DONE
Details
Telephone call  2/19/2016 DONE
Rob called asking why he was unable to schedule any inspections. Informed him that I had spoke with BJ on Wednesday, 2-17, letting him know that it needed to be pulled by fixture and not value. Told Rob that BJ emailed me the fixtures and I placed them in there and emailed BJ back informing him that there is a fee of $900 due. See documents for email
Conference2/17/20162/17/20162/17/2016PDONE
DetailsChad Schwendiman
Monte 9724667 Inspection requested via web by william kerwin - Need installation instructions for fire dampers to be able to approve.
Rough-in2/17/20162/17/20162/17/2016PCANC
DetailsChad Schwendiman
Rob ###-####
Telephone call  2/17/2016 DONE
Spoke with BJ and I informed him that he can email me the fixtures for this project and I would change that for him. He stated he would do that email right away. 8:30am
Issue PAID IN FULL permit  2/12/2016 DONE
Payment received via Govolutions
Application received  2/12/2016 DONE
This permit was created on the web by william kerwin