Final | 4/26/2016 | 4/27/2016 | 4/27/2016 | A | PASS |
Alan Hauser
|
|
|
|
Final | 4/25/2016 | 4/26/2016 | 4/26/2016 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Worley - no access
|
Rough-in | 3/7/2016 | 3/8/2016 | 3/8/2016 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Worley
|
Pressure Test | 2/29/2016 | 3/2/2016 | 3/2/2016 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Worley - 20lb gas pass
|
Rough-in | 2/29/2016 | 3/2/2016 | 3/2/2016 | A | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Worley - not allowed to draw fresh air from the roof, duct work size and routing doesn't match the manual J, need r/a transfers in the bedrooms.
|
Issue PAID IN FULL permit | | | 2/29/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/29/2016 | | DONE |
|
|
|
This permit was created on the web by Troy Worley
|