Final | 6/2/2016 | 6/2/2016 | 6/2/2016 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves
|
Final | 5/31/2016 | 6/1/2016 | 6/1/2016 | A | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves - Need manufactures specs showing combustion air okay with less than 133sq. inches
|
Final | 5/23/2016 | 5/24/2016 | 5/24/2016 | A | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves - Combustion air in mechanical room not installed per approved drawing, Not enough combustion air for appliances in the mechanical room. no access into the main part of the building
|
Pressure Test | 3/14/2016 | 3/15/2016 | 3/15/2016 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves - 60lb gas pass
|
Rough-in | 3/14/2016 | 3/15/2016 | 3/15/2016 | A | PART |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves - Okay to cover walls and ceiling. Need approval from engineer for changes to combustion air
|
Issue PAID IN FULL permit | | | 3/6/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/4/2016 | | DONE |
|
|
|
This permit was created on the web by Gary Reeves
|
First Notice | 6/2/2016 | 6/2/2016 | | | |
Chad Schwendiman
|
|
|
|