Final | 6/14/2016 | 6/17/2016 | 6/17/2016 | A | PASS |
Chad Schwendiman
|
|
|
Rick ###-#### Phone #: ###-#### Inspection requested via web by Jason Robinson
|
Rough-in | 3/17/2016 | 3/17/2016 | 3/17/2016 | P | PASS |
Chad Schwendiman
|
|
|
Inspection requested via web by Jason Robinson
|
Rough-in | 3/16/2016 | 3/17/2016 | 3/17/2016 | A | FAIL |
Chad Schwendiman
|
|
|
Rick ###-#### Phone #: ###-#### Inspection requested via web by Jason Robinson - corrections haven't been made yet, had a confrence to discuss fixing them. need to reschedule rough in when complete
|
Conference | 3/16/2016 | 3/17/2016 | 3/17/2016 | A | DONE |
Chad Schwendiman
|
|
|
Please call Tim to discuss clearance issue and possibley meet on-site. ####-#### or call Jason ###-####. Thx Inspection requested via web by Jason Robinson - met on site to discuss what needs to be done to fix correction.
|
Fees Due Hold | 3/17/2016 | | 3/17/2016 | | DONE |
|
|
|
|
Rough-in | 3/16/2016 | 3/16/2016 | 3/16/2016 | P | FAIL |
Chad Schwendiman
|
|
|
Inspection requested via web by Jason Robinson - still need clearance to combustables on back of fireplace. combustion air piping needs to terminate outside
|
Reinspection Fee (no hold) | 3/16/2016 | 3/16/2016 | 3/16/2016 | P | PASS |
Chad Schwendiman
|
|
|
Reinspection fee failed rough in 3 times
|
Rough-in | 3/14/2016 | 3/15/2016 | 3/15/2016 | A | FAIL |
Chad Schwendiman
|
|
|
Rick ###-#### Phone #: ###-#### Inspection requested via web by Jason Robinson 1) Need clearance to conbustables on the back of the fireplace and the vent per manufactures instructions, 2) Need fire blocking at attic penetration 3) Combustion air needs to terminate per manufactures instructions.
|
Rough-in | 3/8/2016 | 3/10/2016 | 3/10/2016 | A | FAIL |
Chad Schwendiman
|
|
|
Inspection requested via web by Jason Robinson - Rough in is not complete
|
Rough-in | 3/7/2016 | 3/9/2016 | 3/8/2016 | A | CANC |
Chad Schwendiman
|
|
|
>> Inspection requested via web by Jason Robinson Inspection cancelled from web by: Jason Robinson
|
Issue PAID IN FULL permit | | | 3/7/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/7/2016 | | DONE |
|
|
|
This permit was created on the web by Jason Robinson
|