Homeowner Online - Alteration or Repair: Ductless heat pump system for main living room/kitchen and bedroom.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/21/20172/22/20172/22/2017PPASS
DetailsBen Livingston
Phone #: ###-#### Inspection requested via web by Victoria Craig
Final2/20/20172/21/20172/21/2017AFAIL
DetailsBen Livingston
Phone #: ###-#### Inspection requested via web by Victoria Craig
need uv tape on armaflex
Mec-Aging Inspection1/16/20171/16/20171/17/2017 PEND
DetailsBen Livingston
Rough-in10/17/201610/18/201610/18/2016APASS
DetailsBen Livingston
Victoria Phone #: ###-####
Pressure Test10/17/201610/18/201610/18/2016APASS
DetailsBen Livingston
Victoria Phone #: ###-####
20lb gas, and piping
Rough-in10/16/201610/17/201610/17/2016PPART
DetailsBen Livingston
Rough Mechanical for cover.
Thanks,
Brad Phone #: ###-#### Inspection requested via web by Victoria Craig
fireplace ok,
flash shield gas pipe and fittings are not connected per manufactures instructions
Rough-in10/12/201610/12/201610/12/2016PFAIL
DetailsBen Livingston
Victoria// insp. for fireplace//please call ahead Phone #: ###-####
gas piping needs to be installed per manufactures instalation instructions and with approved products,
linesets need nail plates
flex tube isnot an approved product for in wall condensate piping
need fire caulk on fireplace draft stop
Pressure Test10/12/201610/12/201610/12/2016PFAIL
DetailsBen Livingston
Victoria// please call ahead Phone #: ###-####
need to make corrections and retest
Issue PAID IN FULL permit  4/6/2016 DONE
Payment received via Govolutions
Application received  4/6/2016 DONE
This permit was created on the web by Victoria Craig