Final | 7/9/2016 | 7/11/2016 | 7/11/2016 | A | PASS |
Alan Hauser
|
|
|
|
Final | 7/8/2016 | 7/8/2016 | 7/8/2016 | P | CANC |
Alan Hauser
|
|
|
Phone #: ###-#### >> Inspection requested via web by Denton Fuehrer Inspection cancelled from web by: Denton Fuehrer
|
Rough-in | 5/20/2016 | 5/23/2016 | 5/23/2016 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Denton Fuehrer
|
Rough-in | 5/19/2016 | 5/20/2016 | 5/20/2016 | A | FAIL |
Bill VanDegrift
|
|
|
Phone #: ###-#### Inspection requested via web by Denton Fuehrer 1) screws penetrating the inner liner of the b-vent at the second floor floor level, 2) provide ACCA report 3) 20# gas test and 5# flue test ok
|
Issue PAID IN FULL permit | | | 5/18/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/18/2016 | | DONE |
|
|
|
This permit was created on the web by Denton Fuehrer
|