Permit Information
Permit NumberMEC16-02501
StatusFinaled
Name ADVANCED HEATING & COOLING
Site Address 500 S CAPITOL BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Supply and install ERV units and Makeup air units, Air cooled units, gas fired duct heater, HRVs, multiple Ceiling fan coil units, multiple indoor ducted fan coil units, refrigeration piping, electric duct heater, electric ceiling heaters, rooftop supply
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Print Statement  3/16/2018 DONE
First Notice2/9/20172/9/20172/6/2018 DONE
DetailsChad Schwendiman
Print Statement  2/6/2018 DONE
DetailsChristina Prado
Final2/8/20172/9/20172/9/2017APASS
DetailsChad Schwendiman
Request for final inspection. Please contact Larry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
Final2/7/20172/8/20172/8/2017PFAIL
DetailsChad Schwendiman
Request for final inspection. Please contact Larry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - need to complete uv protection on linesets, need to finish missing fire damper access labels
Final2/2/20172/3/20172/3/2017PPART
DetailsBen Livingston
Request for Final inspection. Please contact Larry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
finish firedamper access labels, finish fireplace trim, linesets on roof need uv protection,
pandeck needs to be cut for roof access
Final1/13/20171/13/20171/13/2017PPART
DetailsChad Schwendiman
Temporary occupancy okay for 1st through 4th floors
Final1/11/20171/12/20171/12/2017PFAIL
DetailsChad Schwendiman
Request for Final inspection floors 1-4. Please contact Larry ###-#### or Jerry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - need air balance report for 1st through 4th floors
Rough-in1/10/20171/11/20171/11/2017APART
DetailsChad Schwendiman
Request for cover inspection for 2 penthouse suites 6th floor. Please contact Larry ###-#### or Jerry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover penthouse ceilings
Rough-in1/4/20171/6/20171/6/2017ACANC
DetailsChad Schwendiman
Request for cover inspection Capital side of the building corridor on 6th Floor. Please contact Jerry ###-#### or Larry ###-#### with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery
Rough-in1/5/20171/5/20171/5/2017PPART
DetailsChad Schwendiman
Jerry Phone #: ###-#### - okay to cover 6th floor corridoor
Rough-in1/4/20171/4/20171/4/2017PFAIL
DetailsChad Schwendiman
Request for cover inspection Capital side of building corridor on 6th Floor. Please contact job lead Larry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Need to install duct mounted access doors for fire/smoke dampers, need to install retaining angles on fire damper at elevator lobby wall
Rough-in12/29/201612/30/201612/30/2016PPART
DetailsChad Schwendiman
Request for 6th Floor R/I inspection Capital side of the building. All except 2 penthouses. Please contact lead, Larry, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover guest rooms on the 6th floor capitol side of the building except for penthouse rooms
Conference12/22/201612/22/201612/22/2016PDONE
DetailsChad Schwendiman
Limited use temporary occupancy okay for 1st floor lobby, second floor okay for guided tours only.
Rough-in12/21/201612/22/201612/22/2016APART
DetailsChad Schwendiman
Request for inspection 6th Floor Myrtle Corridor, 6th Flo elevator lobby, and rooms on Capital Side of 6th Fl. Please contact lead, Jerry, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 6th floor elevator lobby okay to cover. the other areas aren't ready yet
Rough-in12/19/201612/19/201612/19/2016APART
DetailsChad Schwendiman
Temp occupancy inspection request for 1, 2, 3rd floors. Please contact Jerry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Okay for 10 hotel staff to occupy the 1st and second floors.
Rough-in12/16/201612/16/201612/16/2016AFAIL
DetailsChad Schwendiman
Temp occupancy inspection request for 1st, 2nd and 3rd fl. Request for inspection 6th floor myrtle North side of the building. please contact Jerry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - need to label fire damper access panels, need to correct improperly installed fire/smoke damper on 6th floor, need to complete condensate on unit in 2nd floor data room.
Okay to cover guest rooms on 6th floor north side of myrtle
Rough-in12/15/201612/15/201612/15/2016PFAIL
DetailsChad Schwendiman
Temporary occupancy inspection request for 1st and 2nd floor. request for R/I inspection 6th Floor Myrtle North side of the building. Please contact Jerry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - missing duct detector, condensates not complete, ducting needs to be completed
Rough-in12/15/201612/15/201612/15/2016PCANC
DetailsChad Schwendiman
Request for R/I inspection 6th floor Myrtle North side of the building. Please contact Larry ###-#### or Jerry ###-#### with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Rough-in12/14/201612/15/201612/15/2016ACANC
DetailsChad Schwendiman
Request for R/I inspection 6th Floor Myrtle North side of the building. Please contact Larry ###-#### or Jerry ###-#### with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Rough-in12/12/201612/13/201612/13/2016APART
DetailsChad Schwendiman
Request for inspection 6th Floor Myrtle side of building. Please contact job lead, Larry, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover guest rooms on the south side of myrtle on the 6th floor
Rough-in12/2/201612/5/201612/5/2016PPART
DetailsChad Schwendiman
Request for shaft inspection, 6th floor. Please contact job lead, Larry, with any questions or concerns ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover grid ceilings in 1st floor lobby/office area, okay to cover grid ceilings on 2nd foor, okay to cover mechanical shafts on 6th floor
Rough-in12/1/201612/2/201612/2/2016AFAIL
DetailsChad Schwendiman
Inspection request for 1st and 2nd FL cover for grid, Capital side of building. Please contact job lead, Larry, ###-####, with any questions or concerns. Inspection requested via web by Heather Gransbery - need 1/4" per foot of rise on b-vent, need 1" clearance on b-vent, need to complete condensate connections and fresh air to ceiling cassettes, need to verify if fire dmper is needed on fresh air duct into laundry room
Rough-in11/30/201612/1/201612/1/2016PCANC
DetailsChad Schwendiman
Inspection request for 1st and 2nd FL cover for grid, Capital side of building. Please contact job lead, Larry, ###-####, with any questions. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Rough-in11/28/201611/30/201611/30/2016PCANC
DetailsChad Schwendiman
Inspection request for 1st and 2nd FL cover for grid, Capital side of building. Please contact job lead, Larry, ###-####, with any questions. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Rough-in11/17/201611/18/201611/18/2016PPART
DetailsBen Livingston
Request for cover inspection for Capital side of the building 5th Fl corridor and rooms. Please contact Larry, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
5th floor capital side rooms, coridor, 3 chases, ok for cover
Rough-in11/15/201611/15/201611/15/2016PPART
DetailsChad Schwendiman
Request for cover inspection 5th Fl. Corridor on Myrtle and Capital sides of the building. Please contact job lead, Larry, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover cooridoor ceiling on myrtle side of building
Rough-in11/14/201611/15/201611/15/2016PCANC
DetailsChad Schwendiman
Request for cover inspection 5th Fl corridor on Myrtle and Capital sides of building. Cover inspection for rooms on Myrtle side of the building. Please contact job lead, Larry, ###-####, with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Rough-in11/9/201611/9/201611/9/2016PPART
DetailsChad Schwendiman
Inspection request for cover. Rooms on 5th Floor Myrtle side of the building. Please contact lead, Larry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover guest rooms on 5th floor myrtle side except for room 516
Rough-in11/3/201611/4/201611/4/2016APART
DetailsChad Schwendiman
Inspection request for Rm 407, shaft on 5th Floor Myrtle side of building, and corridor on 4th floor Capital side of building. Please contact job lead, Larry, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - room 407 okay to cover, cooridoor ceiling on 4th floor capitol side okay to cover. okay to cover mechanical shafts on 5th floor east of elevator lobby
Rough-in11/1/201611/2/201611/2/2016APART
DetailsBen Livingston
Request for cover inspection 4th Floor Capital side of building. Please contact job lead, Larry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery
407 gas valve for fireplace no access'
rest of rooms on capital side ok
Rough-in10/31/201610/31/201610/31/2016PPART
DetailsChad Schwendiman
Inspection request for corridor of 3rd floor Capitol side of the building and 4th Floor Myrtle side of the building. Please contact Larry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover cooridoor ceilings on 4th floor myrtle side, and 3rd floor capitol side
Rough-in10/26/201610/27/201610/27/2016PPART
DetailsChad Schwendiman
Inspection request for grease duct 2-3 levels. Rest of the rooms 4th floor Myrtle side of the building. Please contact job lead, Larry, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover grease duct in the shaft on the 2nd and 3rd floors. okay to cover guest rooms on 4th floor except for 403, and 412
Conference10/24/201610/24/201610/24/2016PPART
DetailsChad Schwendiman
Inspection request for cover 4th floor Myrtle rooms. Please contact lead, Larry, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Okay to cover ceilings in rooms 418 thru 430
Rough-in10/21/201610/21/201610/21/2016PPART
DetailsChad Schwendiman
Request for inspection on 3rd corridor grease duct shaft and rooms on 4th floor myrtle side of the building. Please contact job lead, Larry ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover 3rd floor cooridoor. 4th floor not ready, and grease duct missing supports and banding
Rough-in10/20/201610/20/201610/20/2016PPART
DetailsChad Schwendiman
Inspection request for Capital side 4th Floor and grease duct shaft. Please contact job lead Larry, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover mechanical shafts on the 4th floor except for the grease duct shaft. 2nd layer of grease duct fail. need to protect where the unistrut passes through the fire wrap, need a 3rd layer of fire wrap over lapping the ul listed zero clearance shell and the 2nd layer of fire wrap 6"
Rough-in10/19/201610/19/201610/19/2016PCANC
DetailsChad Schwendiman
Inspection request for 2nd layer wrap on grease duct. Please contact job lead, Larry ###-####, with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Rough-in10/17/201610/17/201610/17/2016PPART
DetailsChad Schwendiman
Inspection request for 1st layer wrap on grease duct. Please contact job lead, Larry, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 1st layer of fire wrap okay on both grease ducts in the shaft.
Rough-in10/14/201610/17/201610/17/2016APART
DetailsChad Schwendiman
Request for cover inspection 3rd floor. Please contact office at ###-####, Heather with any questions or concerns. Phone #: ###-#### Inspection requested via web by HeatherGransbery - okay to cover 3rd floor cooridoor on the myrtle side of the building
Rough-in10/13/201610/14/201610/14/2016PPART
DetailsChad Schwendiman
Request for cover inspection 3rd floor. Please contact job lead, Larry Halbert, ###-####, with any questions or concerns. Inspection requested via web by Heather Gransbery - okay to cover 3rd floor capitol side guest rooms
Rough-in10/13/201610/13/201610/13/2016PNR
DetailsChad Schwendiman
Request for cover inspection of 3rd floor. Please contact job lead, Larry, ###-#### with any questions or concerns. Inspection requested via web by Heather Gransbery - 3rd floor capitol south side still not ready
Rough-in10/12/201610/13/201610/13/2016APART
DetailsChad Schwendiman
Request for cover inspection of entire 3rd floor. Please contact job lead, Larry Halbert, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 3rd floor capitol side okay to cover the lids on the north side of the cooridoor
Rough-in10/12/201610/13/201610/12/2016PCANC
DetailsChad Schwendiman
Request for cover inspection of 3rd floor. Please contact job lead, Larry, ###-#### with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Rough-in10/11/201610/11/201610/11/2016PFAIL
DetailsChad Schwendiman
Inspection request for 2nd and 3rd floor shafts. Please contact job lead, Larry, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Grease duct is covered up and was never approved to be covered. UL listed grease duct is not installed per manufacture's installation instructions, & specifications.
Rough-in10/7/201610/7/201610/7/2016PPART
DetailsChad Schwendiman
Larry// ###-####// cover inspection for the 2nd floor - okay to cover hallway ceilings on the 2nd floor
Rough-in9/26/20169/26/20169/26/2016PPART
DetailsChad Schwendiman
Cover inspection request for 2nd fl Capital side of the building. Cover inspection 3rd fl Myrtle side of the building. Please contact job lead Larry Halbert ###-#### with any questions or concerns Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover soffits on 2nd floor capitol side of the building, need duct smoke detectors installed on 3rd floor myrtle side
Rough-in9/15/20169/15/20169/15/2016PPART
DetailsChad Schwendiman
R/I cover inspection 2nd fl Capital side of the building. Please contact job lead, Larry Halbert, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested
via web by Heather Gransbery - okay to cover womens bathroom ceiling on 2nd floor. Need access doors and retaining angles on fire damper in mens bathroom
Rough-in9/12/20169/12/20169/12/2016PPART
DetailsChad Schwendiman
Okay to cover guest room ceilings on 2nd floor myrtle side of the building
Rough-in9/1/20169/2/20169/2/2016APART
DetailsChad Schwendiman
Cover inspection for 2nd floor, Myrtle side of building. Please call Larry Halbert with any questions ###-####. Phone #: ###-#### Inspection requested via web by Bailey Esposito - okay to cover fireplace vents on 2nd floor myrtle side of the bldg
Rough-in8/31/20168/31/20168/31/2016PPART
DetailsChad Schwendiman
R/I inspection request for 2nd floor cover. Myrtle side of building. Please contact job lead, Larry, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Okay to cover the fireplace vent soffits in the 2nd floor north side of the myrtle wing only.
Rough-in8/25/20168/26/20168/26/2016PFAIL
DetailsChad Schwendiman
R/I inspection request for 2nd and 3rd floor, Myrtle side of the building. Please contact job lead, Larry Halbert, with any questions or concers ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery - need screws in retaining angles of fire/smoke dampers per manufactures installation instructions, need access doors for smoke/fire dampers. Need protection for fire partition between guest room where fresh air duct passes through.
Rough-in8/24/20168/25/20168/25/2016PCANC
DetailsChad Schwendiman
R/I Inspection request for 3rd floor, Mrytle St side of building. Please contact job lead, Larry Halbert, with any questions or concerns. ###-#### Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Conference8/24/20168/24/20168/24/2016ADONE
DetailsChad Schwendiman
Contractor request for walk through for site inspection. Please contact job lead, Larry Halbert, ###-#### with question or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - walked through with Larry and went over the process for inspecting the fire dampers, and fire/smoke dampers.
Rough-in7/20/20167/21/20167/21/2016PPART
DetailsChad Schwendiman
R/I inspection request for cover on Capitol side of building, 1st Fl. Please contact job lead Larry Halbert, ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - 1st floor okay including sealer on b-vent
Rough-in7/18/20167/20/20167/20/2016PCANC
DetailsChad Schwendiman
R/I inspection request for cover on Capitol side of building, 1st Fl. Please contact job lead Larry Halbert, ###-#### Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Rough-in7/15/20167/18/20167/18/2016PPART
DetailsChad Schwendiman
R/I inspection request. First floor grease duct, Capital side of the building. Please contact job lead, Larry Halbert ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - rough in on 1st floor ductwork pass. need to seal b-vent pipe for hrv on 1st floor still.
Rough-in6/27/20166/29/20166/28/2016ACANC
DetailsChad Schwendiman
R/I inspection on podium. Please contact job lead Larry Halbert, ###-#### with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
Issue PAID IN FULL permit  6/9/2016 DONE
Payment received via Govolutions
Application received  6/9/2016 DONE
This permit was created on the web by Heather Gransbery