Permit Information
Permit NumberMEC16-02723
StatusFinaled
Name THOMAS HEATING & COOLING LLC
Site Address 1714 N 31ST ST
Project NameChenoweth Residence
Customer Number 
ePlanReviewNo
Description
new dutc work, gas piping, ventilation, new gas furnace, central air.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/9/20173/9/20173/9/2017PPASS
DetailsBrian Scoles
please call half hour prior Phone #: ###-#### Inspection requested via web by thomas nguyen-
Mec-Aging Inspection2/20/20172/20/20172/21/2017 PEND
DetailsBen Livingston
Conference11/20/201611/21/201611/21/2016AFAIL
DetailsBen Livingston
please call ahead of time Phone #: ###-#### Inspection requested via web by thomas nguyen

duct on crawl needs to be supported to structure, length need to be limited. need air balance report, and duct blast
need approved condensate fitting on furnace
return plenum cannot have romex in it.
6" fresh air needs to be insulated
bedroom need transer over the door,
flue needs to be refirecaulked
Pressure Test7/21/20167/21/20167/21/2016APASS
DetailsBen Livingston
5lb flue
Conference7/14/20167/15/20167/15/2016ACANC
DetailsBen Livingston
please call Marco half hour priority Phone #: ###-#### Inspection requested via web by thomas nguyen
Rough-in7/15/20167/15/20167/15/2016APART
DetailsBen Livingston
20 lb gas, rough in,,,,,
flue needs to be retested
Rough-in7/14/20167/14/20167/14/2016AFAIL
DetailsBen Livingston
please call half hour priorty Phone #: ###-#### Inspection requested via web by thomas nguyen-
need to make manual j approved for roughin
Application received  6/20/2016  
Issue PAID IN FULL permit  6/20/2016 DONE