First Notice | 6/16/2017 | 6/16/2017 | 8/21/2017 | | DONE |
Chad Schwendiman
|
|
|
This permit finaled on the web by Dan Flaherty
|
Final | 6/16/2017 | 6/16/2017 | 6/16/2017 | P | PASS |
Chad Schwendiman
|
|
|
Contact Stan ###-#### or Dan ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty
|
Final | 6/14/2017 | 6/15/2017 | 6/15/2017 | A | FAIL |
Chad Schwendiman
|
|
|
The owner wants us to call for this Final. Contact Stan ###-#### or Dan ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty - Still haven't recieved the air balance report. all other correction completed
|
Final | 5/24/2017 | 5/26/2017 | 5/26/2017 | A | FAIL |
Chad Schwendiman
|
|
|
Final Mechanical Phone #: ###-#### Inspection requested via web by Kim Adams - Missing angles on firedampers 1st. floor and mezzanine. Missing door louvers on mechanical room 1st floor. Need to complete condensate drains on mezzanine units. Parking garage exhaust fan not running. Need a copy of air balance report from owner, waiting for them to email it to me.
|
Rough-in | 4/12/2017 | 4/12/2017 | 4/12/2017 | P | CANC |
Chad Schwendiman
|
|
|
rough in inspection for the second floor ceiling on North side. Francisco is the contact Phone #: ###-#### Inspection requested via web by Kim Adams
|
Rough-in | 3/28/2017 | 3/28/2017 | 3/28/2017 | P | PART |
Chad Schwendiman
|
|
|
temporary occupancy inspection Phone #: ###-#### Inspection requested via web by Kim Adams - Temporary occupancy okay for 2nd and 4th floors only
|
Final | 3/23/2017 | 3/23/2017 | 3/23/2017 | P | FAIL |
Chad Schwendiman
|
|
|
Looking for a Temp Occupancy for 2nd and 4th floor. Contact Francisco ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty - garage mechanical shaft not complete, no power to fire/smoke dampers on ERV on 2nd floor.
|
Rough-in | 3/21/2017 | 3/22/2017 | 3/22/2017 | A | PART |
Chad Schwendiman
|
|
|
rough in inspection for the garage exhaust Phone #: ###-#### Inspection requested via web by Kim Adams - okay to cover parking garage exhaust duct on mezzanine, and 2nd floor. need to see framing around dampers on 1st floor and 3rd floor
|
Rough-in | 3/17/2017 | 3/20/2017 | 3/20/2017 | A | PART |
Chad Schwendiman
|
|
|
a rough in inspection for the fluid cooler duct Phone #: ###-#### Inspection requested via web by Kim Adams - okay to cover cooling tower duct.
|
Rough-in | 3/2/2017 | 3/3/2017 | 3/3/2017 | A | PART |
Chad Schwendiman
|
|
|
in inspection for ceiling of the mezzanine Phone #: ###-#### Inspection requested via web by Crystal Grant - okay to cover gris ceiling on mezzanine, okay to cover duct in north west shaft on 2nd floor
|
Conference | 2/28/2017 | 2/28/2017 | 2/28/2017 | A | DONE |
Chad Schwendiman
|
|
|
Walk job to see whats needed for temporary occupancy - 1. Fire, and Fire/Smoke dampers installed in openings, or opening temporarily protected to meet the same rating as required for dampers (1hr, 2hr, ect.) 2. The ERV’s that serve the area being occupied need to be complete, and operational to provide ventilation/exhaust air to that area. 3. The parking garage exhaust need to be completed and operational prior to being able to occupy the garage. 4. The boiler needs to be operational to provide heat to the occupied areas. 5. The heat pumps in the occupied area need to be complete and operational to provide heat to the areas. 6. The issues with the boiler venting need to be resolved. (this is Mountain West Mechanicals issue)
|
Conference | 2/23/2017 | 2/24/2017 | 2/24/2017 | A | DONE |
Chad Schwendiman
|
|
|
Please call Stan when you are ready to coordinate with structural inspector as well. Phone #: ###-#### Inspection requested via web by Crystal Grant - meet on site to discuss fire/smoke dampers in shafts
|
Rough-in | 2/16/2017 | 2/17/2017 | 2/17/2017 | A | PART |
Chad Schwendiman
|
|
|
second floor Phone #: ###-#### Inspection requested via web by Crystal Grant - okay to cover ceilings in rooms except for 215, 216, 229
|
Rough-in | 1/27/2017 | 1/27/2017 | 1/27/2017 | P | PART |
Chad Schwendiman
|
|
|
2nd floor rough in Phone #: ###-#### Inspection requested via web by Crystal Grant - okay to cover rooms 220, 223, 231-244, 248
|
Rough-in | 1/17/2017 | 1/18/2017 | 1/17/2017 | A | CANC |
Chad Schwendiman
|
|
|
Shaft inspection contact Francisco ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty
|
Rough-in | 1/17/2017 | 1/17/2017 | 1/17/2017 | P | FAIL |
Chad Schwendiman
|
|
|
Shaft inspection Phone #: ###-#### Inspection requested via web by Crystal Grant - need installation instructions for fire/smoke dampers
|
Rough-in | 12/5/2016 | 12/5/2016 | 12/5/2016 | P | PASS |
Troy James
|
|
|
mezzanine unit numbers 6, 7 and 8 Phone #: ###-#### Inspection requested via web by Crystal Grant ok to cover ducts at mezzanine from service elevator to the east. Three trunck lines with branches.
|
Rough-in | 11/16/2016 | 11/16/2016 | 11/16/2016 | P | PART |
Ben Livingston
|
|
|
soffits on the first floor Phone #: ###-#### Inspection requested via web by Crystal Grant 1st floor soffits ok for cover
|
Rough-in | 10/6/2016 | 10/7/2016 | 10/7/2016 | A | PART |
Chad Schwendiman
|
|
|
Mezzanine restrooms. Phone #: ###-#### Inspection requested via web by Crystal Grant - okay to cover bathroom ceilings
|
Rough-in | 9/30/2016 | 10/3/2016 | 10/3/2016 | A | PART |
Chad Schwendiman
|
|
|
2nd floor cover inspection Phone #: ###-#### Inspection requested via web by Crystal Grant - okay to insulate duct work on 2nd floor
|
Rough-in | 9/27/2016 | 9/27/2016 | 9/27/2016 | P | PART |
Chad Schwendiman
|
|
|
Francisco-3rd floor restrooms Phone #: ###-#### Inspection requested via web by Crystal Grant -okay to cover 3rd floor bathroom ceiling's
|
Rough-in | 9/22/2016 | 9/22/2016 | 9/22/2016 | P | PART |
Chad Schwendiman
|
|
|
Second Floor bathrooms Phone #: ###-#### Inspection requested via web by Crystal Grant - okay to cover 2nd floor bathroom ceilings
|
Rough-in | 8/4/2016 | 8/4/2016 | 8/4/2016 | P | PART |
Chad Schwendiman
|
|
|
Kyle/4th floor bathrooms Phone #: ###-#### Inspection requested via web by Crystal Grant okay to cover ceilings in 4th floor bathrooms
|
Rough-in | 8/1/2016 | 8/1/2016 | 8/1/2016 | P | CANC |
Chad Schwendiman
|
|
|
Kyle/4th floor restrooms. Phone #: ###-#### Inspection requested via web by Crystal Grant - Building permit has not been issued
|
Issue PAID IN FULL permit | | | 6/30/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/30/2016 | | DONE |
|
|
|
This permit was created on the web by Crystal Grant
|