Final | 11/2/2016 | 11/2/2016 | 11/2/2016 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek
|
Final | 11/1/2016 | 11/1/2016 | 11/1/2016 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek- need drip leg on gas line at furnace- need combustion air to furnace room
|
Rough-in | 8/30/2016 | 8/30/2016 | 8/30/2016 | P | PASS |
Brian Scoles
|
|
|
Reinspection Phone #: ###-#### Inspection requested via web by Andrea Creek- 20lb gas pass- 5lb flue pass
|
Rough-in | 8/29/2016 | 8/29/2016 | 8/29/2016 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek - living room supplies show 1-6x14 and 1-4x12 ran with1-4x14 and 1-4x10- master bedroom shows 1-6x14 ran with 14x14- left correction notice front window
|
Pressure Test | 8/29/2016 | 8/29/2016 | 8/29/2016 | P | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek - 20lb gas pass- cant reach flue pressure gauge
|
Issue PAID IN FULL permit | | | 8/26/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/26/2016 | | DONE |
|
|
|
This permit was created on the web by Andrea Creek
|