Final | 4/10/2017 | 4/10/2017 | 4/10/2017 | P | PASS |
Brian Scoles
|
|
|
Inspection requested via web by Floyd Floyd Peek
|
Final | 4/6/2017 | 4/7/2017 | 4/7/2017 | P | FAIL |
Brian Scoles
|
|
|
Please call Max to meet at job, ###-####, Thanks Inspection requested via web by Floyd Floyd Peek- a/C does not match manual J- flue exhaust needs to be 3' from forced air inlet-- Went over on jobsite with Max
|
Rough-in | 11/21/2016 | 11/21/2016 | 11/21/2016 | P | PASS |
Brian Scoles
|
|
|
Call max ###-#### to meet on the job Inspection requested via web by Floyd Floyd Peek- equipment not set- rough in pass
|
Pressure Test | 11/21/2016 | 11/21/2016 | 11/21/2016 | P | PASS |
Brian Scoles
|
|
|
Call max ###-#### to meet on the job Inspection requested via web by Floyd Floyd Peek- 20lb gas pass- 5lb flue pass
|
Conference | 11/21/2016 | 11/21/2016 | 11/21/2016 | P | CANC |
Chad Schwendiman
|
|
|
Call max ###-#### to meet on the job >> Inspection requested via web by Floyd Floyd Peek Inspection cancelled from web by: Floyd Floyd Peek
|
Rough-in | 11/16/2016 | 11/16/2016 | 11/16/2016 | A | FAIL |
Brian Scoles
|
|
|
Call Max for door code or to meet you on the job. ###-#### Inspection requested via web by Floyd Floyd Peek 1- need approved manual J insite 2- b vent needs 1" clearance to combustibles floor and up wall 3- gas presure test below 20 lbs 4- need combustion air 5- register in kitchen along stairwell wall missing 6-need another supply register in family room basement 7- need 6" outside air to R/A plenum 8-bedroom #1 needs supply completed 9- dryer vent needs hangers every 4' and in wall and framing needs completed for ceiling 10- seal all duct work and mastic registers to floor 11- frame in around bedroom #1 R/A in closet needs finished Went over all issues with Max onsite- left correction notice onsite
|
Pressure Test | 11/16/2016 | 11/16/2016 | 11/16/2016 | A | PASS |
Brian Scoles
|
|
|
Call Max for door code or to meet you on the job. ###-#### Inspection requested via web by Floyd Floyd Peek- 5lb flue pass
|
Rough-in | 11/4/2016 | 11/4/2016 | 11/4/2016 | P | CANC |
Chad Schwendiman
|
|
|
Call Max ###-#### for acess >> Inspection requested via web by Floyd Floyd Peek Inspection cancelled from web by: Floyd Floyd Peek
|
Issue PAID IN FULL permit | | | 11/4/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/4/2016 | | DONE |
|
|
|
This permit was created on the web by Floyd Floyd Peek
|