Final | 4/19/2017 | 4/19/2017 | 4/19/2017 | P | PASS |
Ben Livingston
|
|
|
The unit will fit thru the Attis access with a 1/2" to spare. Phone #: ###-#### Inspection requested via web by Tony Fogg attic access I will pass per your measurements.
|
Final | 4/18/2017 | 4/18/2017 | 4/18/2017 | P | FAIL |
Ben Livingston
|
|
|
If the duplex is locked the keys are in the electrical panel on the back of the house. The manual J should be above the stove in the cabinet. Phone #: ###-#### Inspection requested via web by Tony Fogg need balance report for furnaces, attic access is smaller than what was roughed in, please verify units can be removed for final
|
Rough-in | 11/15/2016 | 11/15/2016 | 11/15/2016 | P | PASS |
Ben Livingston
|
|
|
Rough in reinspection. Phone #: ###-#### Inspection requested via web by Tony Fogg
|
Conference | 11/10/2016 | 11/10/2016 | 11/10/2016 | P | FAIL |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Tony Fogg
condensatesupport needs to be permanently fastened both sides line sets need nail plates both sides 6" fresh air both sides dryer vent needs wall fuered out so pipe can fit in the wall, nail plate also
|
Rough-in | 11/8/2016 | 11/8/2016 | 11/8/2016 | P | FAIL |
Ben Livingston
|
|
|
Rough in is complete on both sides of the duplex. The furnaces are in the attic. Phone #: ###-#### Inspection requested via web by Tony Fogg approved manual j will have Troy James signature, also will have size of fresh air on it. needs approved manual j for inspection
|
Rough-in | 11/7/2016 | 11/8/2016 | 11/8/2016 | A | FAIL |
Eric Strole
|
|
|
Both sides of the duplex are ready for rough in inspection. The furnaces are in the attic mechanical room. Phone #: ###-#### Inspection requested via web by Tony Fogg-Need approved manual-j on site for inspection.
|
Issue PAID IN FULL permit | | | 11/7/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/7/2016 | | DONE |
|
|
|
This permit was created on the web by Tony Fogg
|
Telephone call | | | 11/7/2016 | | DONE |
|
|
|
Left a message for Tony informing him that his permit will need to be done by fixtures not sqft since the duplex was damage due to fire so it would be an alteration not new. Asked him to give me a call so that I can add those fixtures in the permit for him. Fee amount, $30, is incorrect as well.
|