Final | 6/14/2017 | 6/14/2017 | 6/14/2017 | P | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Teresa Costello
|
Mec-Aging Inspection | 6/14/2017 | 6/14/2017 | 6/14/2017 | | CANC |
Chad Schwendiman
|
|
|
BJ is going to get this scheduled for a final
|
Rough-in | 11/17/2016 | 11/17/2016 | 11/17/2016 | A | PASS |
Chad Schwendiman
|
|
|
|
Rough-in | 11/16/2016 | 11/16/2016 | 11/16/2016 | P | FAIL |
Ben Livingston
|
|
|
bj ###-#### >> Inspection requested via web by william kerwin need 6" fresh air to return plenum, dryer vents needs nail plate at floor
|
Rough-in | 11/16/2016 | 11/16/2016 | 11/16/2016 | P | CANC |
Ben Livingston
|
|
|
bj ###-#### >> Inspection requested via web by william kerwin Inspection cancelled from web by: william kerwin
|
Fees Due Hold | 11/15/2016 | | 11/16/2016 | | DONE |
|
|
|
|
Rough-in | 11/11/2016 | 11/14/2016 | 11/14/2016 | P | FAIL |
Chad Schwendiman
|
|
|
Manual J is near the fireplace. Phone #: ###-#### Inspection requested via web by william kerwin - Furnace locaton and duct work doesn't match the approved manual J, Need to revise manual J and resubmit for approval.
|
Rough-in | 11/10/2016 | 11/10/2016 | 11/10/2016 | P | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by william kerwin - still need approved manual J onsite
|
Rough-in | 11/8/2016 | 11/9/2016 | 11/9/2016 | A | FAIL |
Chad Schwendiman
|
|
|
bj ###-#### Inspection requested via web by william kerwin 1) Need approved manual J onsite 2) Need 1" gap between b-vent and insulation shield on water heater vent 3) Need to insulate metal duct in joist space of garage.
|
Pressure Test | 11/8/2016 | 11/9/2016 | 11/9/2016 | A | PASS |
Chad Schwendiman
|
|
|
bj ###-#### Inspection requested via web by william kerwin - 20lb gas pass, 5lb flue pass
|
Issue PAID IN FULL permit | | | 11/8/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/8/2016 | | DONE |
|
|
|
This permit was created on the web by william kerwin
|